Watlow EZ-ZONE
®
PM PID Controller
•
60
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[R;typ]
[R.tyP]
Profile
Ramping Type
[rate]
Rate (81)
[``ti]
Time (143)
Time
Always
Instance 1
Map 1 Map 2
- - - -
4414
0x7A (122)
1
26 (38)
- - - -
uint
RWE
[P;typ]
[P.tyP]
Profile
Profile Type
Set the profile startup
to be based on a set
point or a process
value.
[StPt]
Set Point (85)
[`Pro]
Process (75)
Set Point Always
Instance 1
Map 1 Map 2
2534
4354
0x7A (122)
1
8
- - - -
uint
RWE
[`GSE]
[ gSE]
Profile
Guaranteed Soak
Enable
Enables the guaran-
teed soak deviation
function in profiles.
[`oFF]
Off (62)
[``on]
On (63)
Off
Always
Instance 1
Map 1 Map 2
2530
4350
0x7A (122)
1
6
- - - -
uint
RWE
[GSd1]
[gSd1]
Profile
Guaranteed Soak
Deviation 1
Set the value of the
deviation band that
will be used in all
profile step types. The
process value must
enter the deviation
band before the step
can proceed.
0.0 to 9,999.000°F or units
0.0 to 5,555.000°C
10.0°F or
units
6.0°C
Always
Instance 1
Map 1 Map 2
2532
4352
0x7A (122)
1
7
- - - -
float
RWE
[`Si;a]
[ Si.a]
Profile Event Input
Source Instance A
Set the source for
WE1..
5 to 6
1
Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - -
4390
0x7A (122)
1
0x1A (26)
- - - -
uint
RWES
[`Si;B]
[ Si.b]
Profile Event Input
Source Instance B
Set the source for
WE2..
5 to 6
1
Function
is set to
Compres-
sor.
Instance 1
Map 1 Map 2
- - - -
4392
7A (122)
1
0x1B (27)
- - - -
uint
RWES
[CoM]
[`SEt]
Communications Menu
PCoL]
[PCoL]
Communications 1
Protocol
Set the protocol of this
controller to the proto-
col that this network
is using.
[`Std]
Standard Bus
(1286)
[Mod]
Modbus RTU
(1057)
Modbus
Always if
digit 8 is a
"1".
Instance 1
Map 1 Map 2
2492
2972
0x96 (150)
1
7
- - - -
uint
RWE
`Ad;S]
[ Ad.S]
Communications 1
Address Standard
Bus
Set the network ad-
dress of this control-
ler. Each device on the
network must have a
unique address.
The Zone Display on
the front panel will
display this number.
1 to 16
1
Protocol
is set to
Standard-
bus.
Instance 1
Map 1 Map 2
2480
2960
0x96 (150)
1
1
- - - -
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set