Watlow EZ-ZONE
®
PM PID Controller
•
44
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`S;hi]
[ S.hi]
Analog Input (1)
Scale High
Set the high scale for
process inputs. This
value, in millivolts,
volts or milliamps,
will correspond to the
Range High output of
this function block.
-100.0 to 1,000.0
20.0
Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter 1 kΩ.
Instance 1
Map 1 Map 2
390
390
0x68 (104)
1
0x10 (16)
7
float
RWES
[`r;Lo]
[ r.Lo]
Analog Input (1)
Range Low
Set the low range for
this function block's
output.
-1,999.000 to 9,999.000
0.0
Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter 1 kΩ.
Instance 1
Map 1 Map 2
392
392
0x68 (104)
1
0x11 (17)
8
float
RWES
[`r;hi]
[ r.hi]
Analog Input (1)
Range High
Set the high range for
this function block's
output.
-1,999.000 to 9,999.000
9,999
Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter 1 kΩ.
Instance 1
Map 1 Map 2
394
394
0x68 (104)
1
0x12 (18)
9
float
RWES
[`P;EE]
[ P.EE]
Analog Input (1)
Process Error En-
able
Turn the Process Er-
ror Low feature on
or off.
[`off]
Off (62)
[Low]
Low (53)
Off
Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter 1 kΩ.
Instance 1
Map 1 Map 2
418
388
0x68 (104)
1
0x1E (30)
10
uint
RWES
[`P;EL]
[ P.EL]
Analog Input (1)
Process Error Low
If the process value
drops below this
value, it will trigger
an input error.
-100.0 to 1,000.0
0.0
Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter 1 kΩ,
and Error
Enable is
set to Low.
Instance 1
Map 1 Map 2
420
420
0x68 (104)
1
0x1F (31)
11
float
RWES
[``t;C]
[ t.C]
Analog Input (1)
Thermistor Curve
Select a curve to ap-
ply to the thermistor
input.
[```A]
Curve A (1451)
[```b]
Curve B (1452)
[```C]
Curve C (1453)
[CUSt]
Custom (180)
Curve A
Sensor Type
is set to
Thermis-
tor.
Instance 1
Map 1 Map 2
434
434
0x68 (104)
1
20x6 (38)
- - - -
uint
RWES
[``r;r]
[ r.r]
Analog Input (1)
Resistance Range
Set the maximum re-
sistance of the therm-
istor input.
[```5]
5K (1448)
[``10]
10K (1360)
[``20]
20K (1361)
[``40]
40K (1449)
40K
Sensor Type
is set to
Thermis-
tor.
Instance 1
Map 1 Map 2
432
432
0x68 (104)
1
0x25 (37)
- - - -
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set