Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`o;hi]
[ o.hi]
Output (1 to 2)
High Power Scale
The power output will
never be greater than
the value specified
and will represent the
value at which output
scaling stops.
0.0 to 100.0%
100.0%
Source is
set to PID
Heat or
Cool.
Instance 1
Map 1 Map 2
898
1018
Offset to next
instance (
Map
1 & Map 2
)
30
0x6A (106)
1 to 2
0xA (10)
88
float
RWES
[`o;ty]
[ o.ty]
Output (1 process)
Type
Select whether the
process output will
operate in volts or
milliamps.
[uoLt]
Volts (104)
[`MA]
Milliamps (112)
Volts
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
720
840
0x76 (118)
1
1
95
uint
RWES
[``Fn]
[ Fn]
Output Process (1)
Function
Set the type of func-
tion that will drive
this output.
[`oFF]
Off (62)
[dupl]
Duplex (212)
[Cool]
Cool (20)
[heat]
Heat (36)
[rmt]
Retransmit (213)
[Ent;b]
Profile Event Out
B (234)
[Ent;A]
Profile Event Out
A (233)
[ALM]
Alarm (6)
Off
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
722
842
0x76 (118)
1
2
96
uint
RWES
[`r;Sr]
[ r.Sr]
Output (1 process)
Retransmit Source
Select the value that
will be retransmitted.
[``Ai]
Analog Input (142)
[StPt]
Set Point (85)
[CUrr]
Current (22)
Analog
Input
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
724
844
0x76 (118)
1
3
97
uint
RWES
[``Fi]
[ Fi]
Output (1 process)
Function Instance
Set the instance of
the function selected
above.
1 to 4
1
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
726
846
0x76 (118)
1
4
98
uint
RWES
[`S;Lo]
[ S.Lo]
Output (1 process)
Scale Low
Set the minimum
value of the output
range.
-100.0 to 100.0
0.00
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
736
856
0x76 (118)
1
9
99
float
RWES
[`S;hi]
[ S.hi]
Output (1 process)
Scale High
Set the maximum
value of the output
range.
-100.0 to 100.0
10.00
Always if
digit 6 of
the part
number is
an "F".
Instance 1
Map 1 Map 2
738
858
0x76 (118)
1
0xA (10)
100
float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S: