Watlow EZ-ZONE
®
PM PID Controller
•
33
•
Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range
Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`dio]
[oPEr]
Digital Input/
Output Menu
[`do;S]
[ do.S]
Digital Output (5 to 6)
Output State
View the state of this
output.
[`off]
Off (62)
[``on]
On (63)
Direction
(Setup Page,
Digital In-
put/Output
Menu) is set
to Output.
Instance 1
Map 1
Map 2
1012
1132
Offset to next
instance equals
+30
0x6A (106)
1 to 2
7
90
uint
R
[`ei;S]
[ Ei.S]
Digital Input (5 to 6)
Event Status
View this event input
state.
[`off]
Off (62)
[``on]
On (63)
Direction
(Setup Page,
Digital In-
put/Output
Menu) is
set to Input
Voltage or
Input Dry
Contact.
Instance 1
Map 1
Map 2
1328
1568
Offset to next
instance equals
+20
0x6E (110)
1 to 2
5
140
uint
R
EZ-Key/s (1 to 2)
Event Status
View this event input
state.
[`off]
Off (62)
[``on]
On (63)
Instance 1
Map 1
Map 2
1368
1608
Instance 2
Map 1
Map 2
- - - -
1628
0x6E (110)
3 to 4
5
140
[LiM]
[oPEr]
Limit Menu
[`LL;S]
[ LL.S]
Limit (1)
Low Set Point
Set the low process
value that will trigger
the limit.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Limit Sides
(Setup Page)
is not set to
High.
Instance 1
Map 1
Map 2
684
724
0x70 (112)
1
3
38
float
RWES
[`Lh;S]
[ Lh.S]
Limit (1)
High Set Point
Set the high process
value that will trigger
the limit.
-1,999.000 to
9,999.000°F or units
-1,128.000 to
5,537.000°C
0.0°F or
units
-18.0°C
Limit Sides
(Setup Page)
is not set to
Low.
Instance 1
Map 1
Map 2
686
726
0x70 (112)
1
4
39
float
RWES
[Mon]
[oPEr]
Monitor Menu
[C;MA]
[C.MA]
Monitor (1)
Control Mode Active
View the current con-
trol mode.
[`off]
Off (62)
[AUto]
Auto (10)
[MAn]
Manual (54)
Always
Instance 1
Map 1
Map 2
1882
2362
0x97 (151)
1
2
- - - -
uint
R
[`h;Pr]
[ h.Pr]
Monitor (1)
Heat Power
View the current heat
output level.
0.0 to 100.0%
0.0
Heat algo-
rithm is not
set to Off.
(Setup Page)
Instance 1
Map 1
Map 2
1904
2384
0x97 (151)
1
0xD (13)
- - - -
float
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other inter-
faces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EEPROM
S: User
Set