Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[``Ai]
[`Set]
Analog Input Menu
[`Sen]
[ SEn]
Analog Input (1)
Sensor Type
Set the analog sen-
sor type to match the
device wired to this
input.
Note:
There is no open-sensor
detec-
tion for process inputs.
[`oFF]
Off (62)
[``tC]
Thermocouple (95)
[`mu]
Millivolts (56)
[uolT]
Volts dc (104)
[`MA]
Milliamps dc (112)
[r0;1H]
RTD 100 Ω (113)
[r1;0H]
RTD 1,000 Ω (114)
[`Pot]
Potentiometer 1
kΩ (155)
[thEr]
Thermistor (229)
Always
Instance 1
Map 1 Map 2
368
368
0x68 (104)
1
5
3
uint
RWES
[`Lin]
[ Lin]
Analog Input (1)
Linearization
Set the linearization
to match the thermo-
couple wired to this
input.
[```b]
B (11)
[```H]
K
(48)
[```C]
C (15)
[```n]
N
(58)
[```d]
D (23)
[```r]
R
(80)
[```E]
E (26)
[```S]
S
(84)
[```F]
F (30)
[```t]
T
(93)
[```J]
J (46)
J
Sensor Type
is set to
Thermo-
couple.
Instance 1
Map 1 Map 2
370
370
0x68 (104)
1
6
4
uint
RWES
[`Rt;L]
[ rt.L]
Analog Input (1)
RTD Leads
Set to match the
number of leads on
the RTD wired to this
input.
[```2]
2 (1)
[```3]
3 (2)
2
Sensor Type
is set to
RTD 100
Ω or RTD
1,000 Ω.
Instance 1
Map 1 Map 2
372
368
0x68 (104)
1
7
- - - -
uint
RWES
[Unit]
[Unit]
Analog Input (1)
Units
Set the type of units
the sensor will mea-
sure.
[`A;tP]
Absolute Tempera-
ture (1540)
[``rh]
Relative Humidity
(1538)
[`Pro]
Process (75)
[PWr]
Power (73)
Process
Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter 1 kΩ.
Instance 1
Map 1 Map 2
- - - -
442
0x68 (104)
1
0x2A (42)
5
uint
RWES
[`S;Lo]
[ S.Lo]
Analog Input (1)
Scale Low
Set the low scale for
process inputs. This
value, in millivolts,
volts or milliamps,
will correspond to the
Range Low output of
this function block.
-100.0 to 1,000.0
0.0
Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter 1 kΩ.
Instance 1
Map 1 Map 2
388
388
0x68 (104)
1
0xF (15)
6
float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set