![Watlow Ez-Zone PM6 Скачать руководство пользователя страница 72](http://html1.mh-extra.com/html/watlow/ez-zone-pm6/ez-zone-pm6_user-manual_3746735072.webp)
Watlow EZ-ZONE
®
PM PID Controller
•
69
•
Chapter 8 Factory Page
Factory Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears in
Menu When
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`LoC]
[FCty]
Security Setting Menu
[LoC;o]
[LoC.o]
Security Setting
Operations Page
Change the security
level of the Opera-
tions Page.
1 to 3
2
Always
- - - -
- - - -
- - - -
- - - -
[LoC;P]
[LoC.P]
Security Setting
Profiling Page
Change the security
level of the Profiling
Page.
1 to 3
3
Always
- - - -
- - - -
- - - -
- - - -
[pas;e]
[LoC.P]
Security Setting
Password Enable
Turn security fea-
tures on or off.
[`off]
Off
[``on]
On
Off
Always
- - - -
- - - -
- - - -
- - - -
[rLoC]
[rLoC]
Security Setting
Read Lock
Set the read secu-
rity clearance level.
The user can access
the selected level
and all lower levels.
If the Set Lockout Se-
curity level is higher
than the Read
Lockout Security,
the Read Lockout
Security level takes
priority.
1 to 5
5
Always
- - - -
- - - -
- - - -
- - - -
[SLoC]
[SLoC]
Security Setting
Write Security
Set the write secu-
rity clearance level.
The user can access
the selected level
and all lower levels.
If the Set Lockout Se-
curity level is higher
than the Read
Lockout Security,
the Read Lockout
Security level takes
priority.
0 to 5
5
Always
- - - -
- - - -
- - - -
- - - -
[loC;l]
[LoC.L]
Security Setting
Locked Access
Level
Determines user
level menu visibility
when security is en-
abled. See Features
section under Pass-
word Security.
1 to 5
5
Always
- - - -
- - - -
- - - -
- - - -
Note: