Watlow EZ-ZONE
®
PM PID Controller
•
49
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range
Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`o;tb]
[ o.tb]
Digital Output (5 to 6)
Time Base
Set the time base
for fixed-time-base
control.
[ 0.1 for Fast and Bi-Di-
rectional outputs, 5.0 for
Slow outputs] to 60
Control
is set to
Fixed
Time
Base.
Instance 1
Map 1 Map 2
1016
1124
Offset to next
instance (
Map
1 & Map 2
)
30
0x6A (106)
5 to 6
3
86
float
RWES
[`o;Lo]
[ o.Lo]
Digital Output (5 to 6)
Low Power Scale
The power output will
never be less than
the value specified
and will represent the
value at which output
scaling begins.
0.0 to 100.0
0.0
Direction is
set to Out-
put and
Source
is set to
Heat or
Cool.
Instance 1
Map 1 Map 2
1016
1136
Offset to next
instance (
Map
1 & Map 2
)
30
0x6A (106)
5 to 6
9
87
float
RWES
[`o;hi]
[ o.hi]
Digital Output (5 to 6)
High Power Scale
The power output will
never be greater than
the value specified
and will represent the
value at which output
scaling stops.
0.0 to 100.0
100.0
Direction is
set to Out-
put and
Source
is set to
Heat or
Cool.
Instance 1
Map 1 Map 2
1018
1138
Offset to next
instance (
Map
1 & Map 2
)
30
0x6A (106)
5 to 6
0xA (10)
88
float
RWES
[`leu]
[ LEv]
Digital Input (5 to 6)
Level
Select which action
will be interpreted as
a true state.
[high]
High (37)
[LoW]
Low (53)
High
Direction
is set to
input
Instance 1
Map 1 Map 2
1320
1560
Offset to next
instance (
Map
1 & Map 2
)
20
0x6E (110)
5 to 6
1
137
uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
*
Available with PM4, PM8 and PM9 models only