4.6. PRE-COMMISSIONING CHECKLIST

 

CAUTION

•  Ensure all service pipes including the heating pipe work is correctly 

installed and leak free.

•  Ensure all isolation valves connected under the boiler are in the fully open 

position

•  Inspect the gas information on the boiler data badge and ensure that the 

gas supply connected to the boiler can deliver the working requirements 
and that the gas supply has been correctly purged before lighting the 
boiler.

•  Check the digital pressure reading on the boiler display screen and ensure 

it is between 1.0 – 1.5 bar when the boiler is cold, and the system has been 
bled of all excess air.

•  Make sure the system and boiler are leak free from any water leakage.
•  Ensure that the PRV is correctly connected to the boiler and that all pipe 

work and termination is installed correctly.

•  Ensure the condense pipe work is connected to the boiler correctly and 

that the pipe work and terminal is fully connected and leak free from any 
water leakage.

•  Check all electrical connections are connected to a 240v ac 50Hz supply 

with suitable isolation.

•  Ensure the appliance is fully and correctly earthed.
•  Check that the electric supply polarity is correct.
•  Check that all external control connections are correct and that 240v ac 

has not been connected directly to the external control connection point 
located on the connection terminal block

THIS LINK MUST BE REMOVED 

AND CONNECTED TO A VOLTAGE 

FREE EXTERNAL CONTROL

•  Ensure all flue connections are correctly made and the flue system is 

correctly supported.

•  Any flue joints need to be fully accessible to comply with the latest 

regulations regarding flues in voids.

•  Check and make sure the flue hole are sealed both internal and external.
•  Ensure the gas supply is free from any gas      leakage and that the ECV is 

fully open.

•  Check that the system has been correctly flushed and that a system 

inhibitor has been added at the correct dosage.

•  Ensure that the appliance is protected by an external 3 amp fuse on the 

incoming mains    electric supply.

•  If an external expansion vessel is installed please ensure the pre charge is 

the same as the pre charge pressure of the expansion vessel located inside 
the boiler.

FLUE INTEGRITY CHECK

 

ATTENTION

Ensure that all flue joints are correctly made and sealed and check the flue 

is suitably supported as per the   manufacturer’s instructions.

Inspect the terminal position and ensure there is no obstruction and make 

sure the flue is sealed through both sides of the wall and if vertically 

installed through the roof space.
Purge your FGA into fresh air and take a note of the O2, CO2 and CO 

reading when successfully purged.
The boiler front cover MUST be correctly fitted and in place when carrying 

out this check.
Operate the boiler in maximum output by either      running a DHW tap or 

put the boiler into service mode (please see page? for instructions).
Remove the air inlet test point on the flue elbow or adaptor and insert your 

FGA, the O2, CO2 and CO    reading whilst the boiler is in operation should 

read the same as it did when purged into fresh air, once this is ok and 

complete insert the cap back into the elbow or adaptor.
Please ensure that the flue is adequately supported at the correct distances 

stated in the flue data section of this manual and that all flue extensions are 

installed with a 3% slope back to the boiler unit.
If the boiler is installed with just the horizontal flue  terminal and no flue 

accessories then the boiler does not require the horizontal flue terminal to 

have a 3% slope back to the boiler as the horizontal terminal has this built 

in so please ensure it is installed level.

4.7. CHECKING INLET GAS PRESSURE

 

ATTENTION

Isolate the appliance at the electrical supply point and turn the gas isolation 

valve off. This is located under the boiler.
Drop down the boiler front control panel and connect a suitable pressure 

gauge to the inlet test point on the gas valve.
Open the gas isolation valve and switch the appliance back on from the 

electrical supply point – caution should be taken as the cables around the 

boiler front control panel maybe live.
Put the boiler into service mode by pressing both Mode and Reset buttons 

together until the circle completes and the boiler display panel will show 

“Lo” press the DHW + button and hold briefly. When released the    display 

panel will show “Hi”, let the appliance settle in high mode for a minimum 

of 2 minutes and then check your pressure gauge and check to see if the 

dynamic       pressure corresponds with the boiler minimum dynamic gas 

pressure as illustrated on the technical data in this manual.
After checking the pressure press both the Mode and Re-set buttons until 

the circle completes and the boiler will revert to the standby display. Isolate 

the power supply to the boiler, close the gas isolation valve and remove the 

pressure gauge from the inlet test point on the gas valve. Ensure the test 

point screw is tight and turn on the gas isolation valve and with a suitable 

LDF test the point for leakage.
Re-assemble the front control panel and boiler cover then switch the power 

supply to the boiler back on.

4.8. TESTING FOR GAS LEAKS DURING USE

 

CAUTION

Using a suitable and certified LDF and taking extreme caution that the 

LDF solution does not come into      contact with any electrical wiring or 

components test all gas joints with the appliance operating in full power by 

operating a DHW tap.
Turn off the appliance at the electrical isolation point and clean up any 

residue LDF.

4.9. CHECK GAS RATE

 

CAUTION

The gas rate should be taken at the meter supplying the boiler and a visual 

inspection of the gas meter should be carried out before commencing to 

ensure it meets all relevant and current regulations and requirements.
The gas rate must be carried out in accordance to the current gas working 

practices.

Содержание Minerwa 25 System IE

Страница 1: ...MinerWa 25 System IE CONDENSING SYSTEM BOILER INSTALLATION SERVICE MANUAL...

Страница 2: ...2 warmhaus com...

Страница 3: ...explanation of its operation The installer is legally required to complete a commissioning checklist as a means of complying with the appropriate Building Regulations England and Wales All installati...

Страница 4: ......

Страница 5: ...N SPLAN WIRING DIAGRAM 28 3 16 4 EXTERNAL CONTROL CONNECTION YPLAN WIRING DIAGRAM 29 4 COMMISSIONING 30 4 1 DISPLAY FUNCTION 30 4 1 1 SET TRANSPARENT PARAMETERS MENU TSP 30 4 1 2 PARAMETERS 31 4 1 3 P...

Страница 6: ...of all statutory regulations These appliances are CE certified for safety and performance and therefore must in no way be altered or have any device or controls fitted unless it is approved in this do...

Страница 7: ...to your user manual and arrange professional assistance where advised Before operating your Warmhaus boiler please read the instructions supplied with the boiler For installation of this appliance in...

Страница 8: ...Combustion Specification G20 G31 Gas Rate Max m h 2 38 0 92 Gas Rate Min m h 0 37 0 11 C02 Maximum Power AUTO CALIBRATION ONLY 8 7 9 2 10 10 5 C02 Minimum Power AUTO CALIBRATION ONLY 8 6 9 4 10 10 5...

Страница 9: ...is can be an exception for a single story open plan dwelling where the living area is more than 70 of the useable floor area in this case this zone can be controlled and treated as a single zone Indiv...

Страница 10: ..._____ Name ___________________________________ Address ___________________________________ ___________________________________ Eircode ___________________________________ Phone Number ________________...

Страница 11: ...ny controls on the boiler All roof space installations should comply to BS5410 part 1 roof space installations Storage Do not store any flammable materials around the location of the boiler or chemica...

Страница 12: ...Debris in the existing heating system can cause damage to the boiler unit and cause efficiency issues and even void the appliance warranty if the correct cleaning has not been carried out 2 7 ELECTRIC...

Страница 13: ...r external corner or to a boundary alongside the terminal 300 I Above ground roof or balcony level 300 J From a surface or a boundary facing terminal 600 K From a terminal facing the terminal 1200 L F...

Страница 14: ...ling of the fixing holes for the mounting bracket can also be done as per the guidance on the wall mounting template The template also displays the pipe centers and correct pipe work layout for the co...

Страница 15: ...es and a connector pipe for the installer to connect to the boiler unit The hardware pack supplied is Flow 22 mm isolation valve compression 2 x Copper end feed adaptor 22 mm to 3 4 Gas 22 mm isolatio...

Страница 16: ...a label if the inhibitor manufacturer supplied this or with a suitable method so that the installation date can be monitored for service Inhibitor levels should be monitored and checked on service ma...

Страница 17: ...d be used with dowels 60 100 mm Concentric ue systems information Only approved Warmhaus flue systems can be connected to our appliance and no other flues have been tested or approved to work with any...

Страница 18: ...CAUTION For security purposes system boiler suction discharge flue should not block even temporarily 3 11 INSTALLATION WITH VERTICAL FLUE SETS 60 100 MM Your system boiler can also be vertically conn...

Страница 19: ...tion and air supply circuits shall fit inside a square of 50 cm and that the distance between the planes of the two orifices shall be less than 50 cm Detail A Waste gas vertical outlet chimney set Roo...

Страница 20: ...1 660 600014 White 153 11 660 600117 Grey 60 100 Condensing Flue Extension L 1000 mm 153 11 660 600111 Black 153 11 660 600015 White 153 11 660 600118 Grey 60 100 Condensing Flue Extension L 2000 mm 1...

Страница 21: ...Gas Installations 2 If the terminal discharges onto a pathway or passageway check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway 3 If a termi...

Страница 22: ...eter 19mm 9 Pipe size transition 10 Minimum internal diameter 30mm 11 Water Weatherproof insulation 12 Drain cover leaf guard INTERNAL CONDENSATE PIPE DISCHARGE TERMINATION External termination to rai...

Страница 23: ...on of a condensate pump typical method 1 Boiler 2 Visible air break at plug hole 3 75 mm sink basin bath or shower waste trap 4 Sink basin bath or shower with integral overflow 5 Open end of condensat...

Страница 24: ...Minimum internal diameter 19 mm 9 Pipe size transition point 10 Minimum internal diameter 30mm 11 Water weather proof insulation EXTERNAL CONNECTIONS External termination to rainwater downpipe NB only...

Страница 25: ...n point 9 Minimum internal diameter 30 mm 10 Water weatherproof insulation 11 Fit drain cover leaf guard INTERNAL CONDENSATE PIPE DISCHARGE TERMINATION Example of a purpose made soakaway 1 Condensate...

Страница 26: ...26 warmhaus com 3 16 MINERWA 25 SYSTEM IE WIRING DIAGRAM WIRING DIAGRAM RISK OF ELECTRIC SHOCK...

Страница 27: ...lied with the boiler To connect your low voltage external control remove the green link wire and connect your two external control cables to the two green wires on the terminal connector 3 16 2 Extern...

Страница 28: ...mains voltage connected to the room stat connections on our terminal connector therefore if the system configuration is an SPLAN please follow the above image to ensure that 240v voltage will not be a...

Страница 29: ...nd must not have voltage connected to the room stat position on our terminal connector therefore if the system configuration is a YPLAN you must connect the relay supplied with our boiler as per the a...

Страница 30: ...ue 0 Attention Do not change this parameter 4 From this moment toggle CH to increase or CH to decrease any parameter aimed to be changed 5 Ones you reach the parameter aimed to be changed Change the p...

Страница 31: ...ter 2 Flow meter AND W O DHW Sensor Algorithm P04 KT coefficient for regulation with EXT probe 4 90 30 P05 Anti fast cycles time value 1 1 minute 0 10 min 3 P06 Maximum CH power 0 100 N A P07 Ignition...

Страница 32: ...hould be SET on the TsP 1 Comfort if this adjusted on TsP then Pre Heat Function is will not work 2 Disable P19 Exhaust measurement configuration 0 1 1 0 Flue thermostad 1 Flue NTC P20 Minimum value f...

Страница 33: ...value 1 10 seconds if Preheat adjusted time value 2 0 60 sec x 10 12 P41 Sanitary modulation with Fluxmeter 0 1 1 0 Disconnected 1 Connected P42 DHW Preheat function configuration Please check P18 fi...

Страница 34: ...Automatic refill valve 5 Not used 6 Recirculation pump 7 Zone valve with OT 8 Not used P52 Automatic water refill 0 1 0 0 Not present 1 Present P53 Parameter perc combustion 0 30 N A P54 Fluxmeter val...

Страница 35: ...flow regulator present 2 4 Not used P67 Button configuration selection 0 1 0 0 Push button only 1 Turning knobes with push button P68 B P paramter 1 DO NOT CHANGE 0 255 63 P69 B P paramter 1 DO NOT C...

Страница 36: ...l Technical data Mark s of conformity Procedure service mode MinerWa 25 System IE granted by Warmhaus R D Pos No Operation Description GB 0 Attention This procedure must be applied by authorised perso...

Страница 37: ...ve the FGA the boiler will now make some tests and when it is ready for adjustment it will display P01 and a setpoint number Step 5 Again as above insert your FGA and check the readings to see if they...

Страница 38: ...ng this time 7 The boiler will be stable within 3 5 minutes after P0 AND set flame correction is displayed on the screen P0 MINIMUM POWER To increase the CO2 value press the DHW button OR to decrease...

Страница 39: ...layed on the screen P0 MINIMUM POWER To increase the CO2 value press the DHW button OR to decrease the CO2 value press the DHW button Attention Calibration range is between 3 and 3 7 After adjusting t...

Страница 40: ...interrrupt Make sure boiler frontal casing is totally closed and sealing of the boiler body is secured during calibration 3 Attention If the OT thermostat is connected to the boiler before start the E...

Страница 41: ...d OFF for 10 cycles ON Time 20sec OFF time 15sec After each switch OFF the counting value will be decreased by 1 14 When 0 is reached the function stops and the boiler exit from the ESF automatically...

Страница 42: ...heck following Informations Last 10 Failure Error codes Information by reading some real values Counters Menu 4 From AL 0 to AL9 show last 10 Error code that boiler had previously Error code shown aft...

Страница 43: ...bove Until OFF symbol shown on the screen 4 The boiler should be OFF 5 Push the RESET and DHW button simultaneously 6 Wait until the approval circle complete on the LCD and release buttons 7 The Air w...

Страница 44: ...t the boiler into service mode please see page for instructions Remove the air inlet test point on the flue elbow or adaptor and insert your FGA the O2 CO2 and CO reading whilst the boiler is in opera...

Страница 45: ...is from a trusted source Warmhaus advise you check the data shown on the calculator routinely by carrying out a gas rate as per the current gas working practices manually and compare the figures If t...

Страница 46: ...ncrease reach the Parameter P02 aimed to be changed 5 Ones you reach the parameter aimed to be changed change the parameter VALUE by using the DHW and set P02 1 6 Push the RESET button to save the adj...

Страница 47: ...le CH to increase reach the Parameter P02 aimed to be changed 5 Ones you reach the parameter aimed to be changed change the parameter VALUE by using the DHW and set P02 0 6 Push the RESET button to sa...

Страница 48: ...ance is maintaining maximum power output and allow the readings on the analyzer to stabilize Readings should be CO less than 300 ppm CO CO2 ratio 0 004 or below Yes Boiler is operating correctly and w...

Страница 49: ...le Combustion Check Ensure the correct fitting of the front casing 5 3 DRAINING THE BOILER CH CIRCUIT CAUTION Isolate the boiler from the electric supply isolation point Carry out electrical safe isol...

Страница 50: ...the 2 screws holding the ignition electrode to the combustion chamber 5 Remove the electrode 6 Fit the new ignition electrode using a new gasket 7 Ensure the correct distances are maintained between t...

Страница 51: ...parameter list 6 Check P15 value on the parameter list 7 Check P22 value on the parameter list 8 Check P44 value on the parameter list 9 Check P46 value on the parameter list 10 If you wish to use th...

Страница 52: ...pull the PRV forward away from the boiler to remove 5 Ensure the new PRV sealing O ring is free from damage and is suitably greased 6 Push the PRV into the hydraulic housing and ensure it correctly lo...

Страница 53: ...place NTC 4 Check cabling and connectors between double NTC and board 5 Reset Restart boiler E 06 No ignition Boiler does not work E06 error code flashing on the screen Gas supply failure 1 RESET boil...

Страница 54: ...be open 4 RESET boiler and check if ok 6 Check Pump operation to check if the pump circulation through the heat exchanger is sufficient 7 Check intermittent contacts on harness carefully check pump a...

Страница 55: ...in accordance with manufacturers instructions and readings are correct yes Gas rate m3 h OR ft3 h Were parts fitted delete as appropriate Yes No Parts fitted System inhibitor concentration has been ch...

Страница 56: ...___________________________________ Account No ___________________________________ Phone Number ___________________________________ Email ___________________________________ RGI Number ______________...

Страница 57: ......

Страница 58: ...IES If you smell gas call Gas Networks Ireland 24 hour emergency line immediately or 1850 20 50 50 Don t assume somebody else has reported the smell Carbon monoxide information For further Information...

Отзывы: