Detail A:
Waste gas vertical outlet chimney set and Pitched Roof Outlet Tile
part installation for Roof
INFORMATION:
The vertical flue terminal can be fitted to both flat
and
pitched
surfaces.
ATTENTION
: For C3 boilers the terminal outlets from separete
combustion and air supply circuits shall fit inside a square of 50
cm and that the distance between the planes of the two orifices
shall be less than 50 cm.
Detail A:
Waste gas vertical outlet chimney set Roof insulation and chimney
transition part
Figure XX Vertical flue set installation application.
Implementation:
L1 = 0.3 m
L2 = 0.5 m. (45° bend equivalent length)
L3 = 2.0 m.
L4 = 0.5 m. (45° bend equivalent length)
L5 = 1.0 m.
L6 = 1.5 m.
L Total =6.3 m. 6.3 m. < Lmax = 11 m.
Correct in implementation.