4.3. CALIBRATION
4.3.1. Auto Calibration
ATTENTION:
This procedure must only be carried by competent
persons and be Gas Safe or RGI registered.
Make sure there is no demand on the boiler before starting the auto
calibration and the front cover is fitted!
Step 1:
Press the reset and CH – buttons together and wait for the approval
circle to complete, TS will be displayed on the LHS of the boiler LCD and
01 on the RHS. Press the CH + button until the number on the RHS reads
14, you will then have 00 displayed in the middle of the screen. Press the
DHW + button until you reach 05 and then press the reset button until the
approval circle completes.
Step 2:
Press the reset and CH – buttons together and wait for the approval
circle to complete, the boiler should now be in the standby mode, then
press the reset and mode buttons together and wait until the approval
circle is complete then let go and within 3 seconds press the CH – button
firmly.
Step 3:
The boiler will now enter the test mode and will carry out several
functions, when the boiler is ready for adjustment it will display P00 and
a setpoint number e.g. 35, at this stage you can insert your FGA into the
boiler and wait to stabilize then using the table below (5446) check to see
if the CO2 or O2 is within the tolerances stated.
Step 4:
If the readings are out of the tolerance then adjust the setpoint
using the DHW + or – buttons to increase or decrease the setpoint number
to change the CO2 or O2 values, once the readings are within the tolerance
press the CH + button and remove the FGA, the boiler will now make some
tests and when it is ready for adjustment it will display P01 and a setpoint
number.
Step 5:
Again as above insert your FGA and check the readings to see
if they are within tolerance, if they require adjustment please follow the
above procedure and when the readings are within the tolerance press the
CH + button and remove the FGA.
Step 6:
The boiler will now carry out some tests and when it is ready for
adjustment it will display P02 and again a setpoint number, now insert your
FGA and check the readings are within tolerance in the below table, follow
the instructions in Step 4 to adjust the readings.
Step 7:
When the readings are ok press the Mode button to exit the AUTO
calibration mode and the boiler will return back to the standby display.
MinerWa 25 System – IE
Combustion & Calibration Values for NATURAL GAS G20
Natural Gas - G 20 (20 mbar)
CO2 (%)
O2 (%)
CO (ppm)
NO
x
(ppm)
Combustion Set Point
Maximum Power= P02= HI
Nominal Value
9.0
5.1
105
26
20
Permitted Tolerance Value
8.8 - 9.2
4.7 - 5.2
90 –120
24-27
16 - 26
Ignition Power= P01
Nominal Value
9.0
5.1
40
17
35
Permitted Tolerance Value
8.8 - 9.2
4.7 - 5.2
35 - 50
13-19
29 - 45
Minimum Power=P00=LO
Nominal Value
9.0
5.1
3
13
55
Permitted Tolerance Value
8.8 - 9.2
4.7 - 5.2
0-10
12-15
36 - 83
MinerWa 25 System – IE
Combustion & Calibration Values for LPG G31
LPG - G 31 (37 mbar)
CO2 (%)
O2 (%)
CO (ppm)
NO
x
(ppm)
Combustion Set Point
Maximum Power= P02= HI
Nominal Value
10.4
5.3
160
15
35
Permitted Tolerance Value
10.0 - 10.5
5.0 - 5.9
120-170
14-25
28 – 46
Ignition Power= P01
Nominal Value
10.4
5.2
65
15
60
Permitted Tolerance Value
10.5 - 10.0
5.0 - 5.9
45—80
10-20
48 - 78
Minimum Power=P00=LO
Nominal Value
10.3
5.3
6
13
38
Permitted Tolerance Value
10.0 - 10.5
5.0 - 5.9
0-10
8-15
25 - 57
DHW
CH