39
warmhaus.com
4.3.3. Manual Calibration
Manual Calibration
Designation:
MinerWa 25 wall-hung boilers
Object
Type-model / Technical data
Mark (s) of conformity
Procedure Manual Calibration
MinerWa 25 System – IE
granted by Warmhaus R&D
Pos No Operation
Description GB
0
Attention:
This procedure must be applied by authorized persons and valid for only condensing boiler.
Attention:
Calibration range is b3 and -3.
Attention:
Set boiler to SUMMER Mode and complete Manual Calibration within 30 minute because time
out is 30 Minute.
1
Press the RESET and MODE button simultaneously.
Attention:
Make sure the all radiator valves are opened and during calibration if boiler cannot reach the
maximum CH limit temperature otherwise calibration process will interrupt. Make sure boiler frontal casing is
totally closed and sealing of the boiler body is secured during calibration.
2
Wait until the approval circle complete on the LCD and release buttons.
3
JUST AFTER RELEASE BUTTONS then Press the CH (-) button within 3 seconds.
4
On the screen "MA-NU" will be displayed and the boiler will try to make ignition attempts. Do not change
gas pressure OR touch to the boiler on this stage!
5
Flame occurrence then boiler will try to determine the size of the flame and make a special cycle to self
adaptation. Do not press any key during this time.
6
The boiler will be stable within 3-5 minutes after P0 AND set flame correction is displayed on the screen.
(P0=MINIMUM POWER).
To increase the CO2 value press the DHW (+) button OR to decrease the CO2 value press the DHW (-)
button. Attention: Calibration range is b3 and -3.
7
After adjusting the P0 value, keep pushing the CH (+) button until the circle complete on the screen then
release to go P1 (IGNITION POWER) “P1” ignition will be displayed on the screen. Then wait 60 seconds for
stabilization.
8
The boiler will be stable within 60 seconds after P1 AND set flame correction is displayed on the screen.
(P1=IGNITION POWER).
To increase the CO2 value press the DHW (+) button OR to decrease the CO2 value press the DHW (-)
button. Attention: Calibration range is b3 and -3.
9
After adjusting the P1 value, keep pushing the CH (+) button until the circle complete on the screen then
release to go P2 (MAXIMUM POWER) “P2” Maximum power will be displayed on the screen. Then wait 60
seconds for stabilization.
10
The boiler will be stable within 60 seconds after P2 AND set flame correction is displayed on the screen.
(P2=MAXIMUM POWER).
To increase the CO2 value press the DHW (+) button OR to decrease the CO2 value press the DHW (-)
button. Attention: Calibration range is b3 and -3.
11
To exit the “MA-NU” calibration push and hold MODE button.
12
Wait until the approval circle complete on the LCD and release MODE button. Manual Calibration procedure
has been completed.
As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Sogutma
Sistemleri San. Tic. A.Ş or be copied or otherwise utilized by anybody without expressed written permission.
Содержание Minerwa 25 System IE
Страница 1: ...MinerWa 25 System IE CONDENSING SYSTEM BOILER INSTALLATION SERVICE MANUAL...
Страница 2: ...2 warmhaus com...
Страница 4: ......
Страница 26: ...26 warmhaus com 3 16 MINERWA 25 SYSTEM IE WIRING DIAGRAM WIRING DIAGRAM RISK OF ELECTRIC SHOCK...
Страница 57: ......