![Warmhaus Minerwa 25 System IE Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/warmhaus/minerwa-25-system-ie/minerwa-25-system-ie_installation-and-service-manual_3434174030.webp)
30
warmhaus.com
SET Transparent Parameters Menu (TSP)
Designation:
MinerWa 25 wall-hung boilers
Object
Type-model / Technical data
Procedure setting or checking TsP parameters
MinerWa 25 System – IE
Pos No Operation
Description GB
0
Attention:
This procedure must be applied by authorized persons and valid for only condensing boiler.
Attention:
The parameters as indicated DO NOT CHANGE should not be adjusted / touched by any official
document supplied by Warmhaus R&D.
1
Press the RESET and CH (-) button simultaneously
2
Wait until the approval circle complete on the LCD and release buttons
3
The screen will appear tSP - Parameter=01 - Value=0
Attention:
Do not change this parameter
4
From this moment toggle CH ( + ) to increase or CH ( - ) to decrease any parameter aimed to be changed
5
Ones you reach the parameter aimed to be changed,
Change the parameter VALUE by using the DHW ( + ) or DHW ( - ) buttons
6
Push the RESET button to save the adjusted value.
Wait until the approval circle complete on the LCD and release button.
7
To exit the TSP menu push the RESET and CH ( - ) simultaneously.
8
Wait until the approval circle complete on the LCD and release buttons. In this way EXIT the TsP Menu
9
Attention:
If parameter P14 set as 5 for Au-To calibration, if the electricity cut OFF / ON - OR wait longer
time than 3 minute the P14 will be reset automatically to=0 so please make calibration just after exit of TsP
4. COMMISSIONING
4.1. DISPLAY FUNCTION
4.1.1. SET Transparent Parameters Menu (TSP)
Содержание Minerwa 25 System IE
Страница 1: ...MinerWa 25 System IE CONDENSING SYSTEM BOILER INSTALLATION SERVICE MANUAL...
Страница 2: ...2 warmhaus com...
Страница 4: ......
Страница 26: ...26 warmhaus com 3 16 MINERWA 25 SYSTEM IE WIRING DIAGRAM WIRING DIAGRAM RISK OF ELECTRIC SHOCK...
Страница 57: ......