17
warmhaus.com
• Loosen the Flange Gasket Screw (6) and remove it from the elbow (1)
• Put the Neoprene Sealing Gasket (7) under the flange and secure it with 4
screws (6 and see Picture A)
• Place the flue elbow (90°) (1) press down and tighten the screw (6) to
secure the flue elbow (see picture B)
• Fit the outer and inner wall flanges (13-14) on the terminal pipe (12)
• Connect flue to the boiler, positioning the seals correctly (picture C). Seal
the flue into the wall with silicone or sand + cement and cover with Wall
Seals provided.
• It is important that the flue terminal must have an horizontal sloping not
less than 1,5 deg. (25 mm per meter) towards the boiler.
3.10. INSTALLING THE FLUE SYSTEM
Apply a suitable lubricant to the sealing joints before connecting any flue
products and ensure the horizontal flue terminal is installed level without a
slope.
The flue pipe must be sealed internally and externally with the wall seals
supplied.
During installation of horizontal pipes, the pipe slope should be
kept at 3% upwards as minimum and at every 3 meter holder
clamps should be used with dowels.
60/100 mm Concentric flue systems information
Only approved Warmhaus flue systems can be connected
to our appliance and no other flues have been tested or
approved to work with any Warmhaus appliances – see
below our list of standard products:
Concealed Flue Configurations
Where our Warmhaus flue system is to be
installed in concealed locations provisions must
be made for inspection and service
requirements.
• Minimum 300 mm square inspection hatches must be fitted.
• The inspection hatch edge must not be fitted more than 1.5 meters away
from a flue joint
• Inspection hatches should be fitted at every change of direction.
Flue Data
60/100mm Concentric flue systems information
Warmhaus flue pipe technical specification:
Horizontal Termination:
• Maximum length = 10 meters including the bend or adaptor connected
directly to the boiler.
• Extensions installed horizontally must have a 3% slope fitted back to the
boiler.
• Effective flue length for the following:
Bend
Equivalent To Straight Length
45 Degree
0.5 meter
90 Degree
1.0 meter
Figure XX Single 90° bended sample flue installation
Figure XX
Installation of
flue set pieces.
Figure XX
Hermetic system
boiler concentric flue
wall output.
Figure XX
Condensing
combi boiler flue
training