- 10 -
General electrical connections
Safety instructions for wiring the heater
Make sure that electrical cables are not damaged. Avoid: chafing, kinking, jamming or exposure to heat.
Electrical connections and ground connections must be free of corrosion and firmly connected.
Things to note about the connections
All connections must be arranged in the craft so that they can function perfectly under normal operating conditions.
Insulate unused cable ends.
The device uses 12 V (nominal) direct current voltage. To minimize current losses, make the power cable as short as
possible and avoid joining. The cross-sectional area of the cable is dependent on the length of the power cords. The
cross-sectional area of the cable should be consistent all the way from the device to the battery. The maximum length
of the power cord is 10 m, based on 6 AWG cable.
The cross-sectional area of the cable
Total length of the power cord (m)
Minimum cross-sectional area of the cable in square mm (US
Gauge)
0-4
2,5 (13 or 12 AWG)
4-6
6 (9 or 8 AWG)
6-10
10 (7 or 6 AWG)
If a thicker cable is required, make a separate joint in the power cord. See picture "Electrical connections of the
device".
Содержание Spartan
Страница 1: ......
Страница 11: ...9 Measures Viking water...
Страница 16: ...14 Installation example 1 Water coolant installation example Wallas on demand hot water accumulator...
Страница 17: ...15 Installation example 2 Water coolant installation example hot water tank calorifier...
Страница 64: ...9 Viking water mitat...
Страница 69: ...14 Esimerkkiasennus 1 Makeavesi l mm nsiirto j rjestelm n esimerkkiasennus Wallas puskuri l mminvesivaraaja...
Страница 70: ...15 Esimerkkiasennus 2 Makeavesi l mm nsiirto j rjestelm n esimerkkiasennus l mminvesivaraaja...
Страница 109: ......