765-1103/100-000
Diagnostics
98
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
Number
(hex)
Alarm
Description
Corrective Action
0x0101
Overvoltage
Overvoltage in supply line 1L
The supply line has exceeded the limiting
value for the maximum voltage.
Check supply voltage
0x0102
Overtemperature
Overtemperature
The device temperature has exceeded the
upper limiting value.
Eliminate external heat
source or overload.
0x0103
Overload
Overload in supply line 1L
The total current in supply line 1L has ex-
ceeded the upper limiting value.
Eliminate overload.
0x0104
Overload, 2L
Overload in supply line 2L
The total current in supply line 1L has ex-
ceeded the upper limiting value.
Eliminate overload.
0x0105
Undertemperature
Undertemperature
The device temperature has fallen below
the lower limiting value.
Thermally insulate the de-
vice
0x0106
Undervoltage, 2L
Undervoltage in supply line 2L
The power supply for supply line 2L has
fallen below the limiting value for the mini-
mum voltage.
Check supply voltage
0x0107
Overvoltage, 2L
Overvoltage in supply line 2L
The power supply for supply line 2L has ex-
ceeded the limiting value for the maximum
voltage.
Check supply voltage
0x0108
Forcing operating mode
active
Forcing operating mode active (activated
by Web client or OPC UA client)
The Web client or OPC UA
client should exit forcing op-
erating mode as soon as
forcing is no longer needed.
0x0109
Short circuit on pin 4
Short circuit detected on pin 4
Eliminate short circuit.
0x010A
Short circuit on pin 2
Short circuit detected on pin 2
Eliminate short circuit.
0x010B
Short circuit on pin 1
Short circuit detected on pin 1.
Eliminate short circuit.