765-1103/100-000
Commissioning
54
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
10
Commissioning
Note
The figures and descriptions below are an example configuration
The figures and descriptions this section contains are based on an example configura-
tion.
Your configuration, and thus the content shown, may differ from the content illustrated
here.
10.1 Setting an IP Address
The module requires an IP address so it can be addressed via the ETHERNET network.
The module has no IP address when delivered. The module can get the IP address in
various ways.
• The PROFINET IO-Controller sets the IP address when PROFINET starts up.
• You can set the IP address permanently or temporarily with the PROFINET engineer-
ing tool of the IO controller. Read the documentation of the PROFINET engineering
tool.
• You can set the IP address with the “ETHERNET Device Configuration” software as
described below. The software is available for download from
ü
kb.hilscher.com/display/ETHDEVCFG
.
Setting the IP Address with the “ETHERNET Device Configuration” Software
•
Launch the “ETHERNET Device Configuration” software.
•
In the menu under
Options
>
Protocols
, verify that the
DCP
option is checked. If the
DCP
option is not checked, check it.
The software lists all the devices found on the local network. Under
IP Address
, ei-
ther 0.0.0.0 (i.e., no IP address set) or the IP address set in the product appears.
•
Click
Search Devices
.