765-1103/100-000
Functions
Product manual | Version: 2.2.0
27
16DO FLD PN DC 24V 2.0A
Table 22: Parameterization Overview
Tool
PROFINET Modules and
Submodules
Port Configuration
PROFINET IO-Controller
The PROFINET IO-Con-
troller configures the
PROFINET modules and
submodules of the Series
765 module.
The IO-Controller sets the parameter the user selects
on the basis of the parameters in the GSDML file.
These parameters configure each individual port and
determine whether the port is used as a digital input or
digital output (or is disabled).
WAGO I/O Field Web-
server
–
Yes
WAGO App I/O Field
–
Yes
WAGO IO-Link Configura-
tor
–
Yes
Note
Parameters via PROFINET are always rewritten upon restart
Each time PROFINET communication starts up, the IO-Controller transfers the configura-
tion and parameters to the 765 Series module. Port configuration parameters that were
set by the WAGO I/O Field Webserver, the WAGO I/O Field app or the OPC UA client are
overwritten. Parameters via PROFINET take precedence.
If you have changed parameters of the port configuration via the WAGO I/O Field Web-
server, the WAGO App I/O Field, the WAGO IO-Link Configurator or the OPC UA Client,
please note that these changes are initially applied by the module, but the I/O controller
overwrites the port configuration again at the next start-up. If you want to change parame-
ters of the port configuration, set them in the configuration software of the I/O controller.
5.5.2 WAGO Webserver I/O Field
The WAGO I/O System Field module has an integrated Webserver. It can be accessed
with a standard Web browser in order to use the following functions:
• Display port information for ports X01, X02 etc.
• Display and modify module settings.
• User setup and management, as well as user login and logout
• Reset module to factory settings and restart firmware.
• Simulating inputs; forcing outputs
Examples of port information include:
• Display current measured values for the digital outputs: temperature, voltage, current
and state on pins 1, 2 and 4
• Display the status information for the entire port
• Configure ports, e.g. set operating mode
• Show process data
The module settings include:
• Select method for obtaining IP address
• Select the origin of the configuration data used
• Display and enter maintenance information
• Reset module to factory settings.
• Load firmware onto the module
• Display and set parameters for Bluetooth
®
connection to the module