765-1103/100-000
Commissioning
88
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
Figure 32: NTP Client Configuration Dialog
3. In the
Input Arguments
section, enter the value 3224725356 for the IP address of
the NTP server in the
ServerIpAddress
field.
4. In the
Input Arguments
section, enter the number 3224725352 for the IP address of
the alternate NTP in the
ServerIpAddressFallback
field.
5. Click
Call
.
ð
If the function was successful, the output field in the
Output Arguments
section to
the right of
Status
shows a value of 0.
A green bar appears in the
Result
section with the text “Succeeded.” The two vari-
ables
ServerIpAddress
and
ServerIpAddressFallback
are now set.
The module retrieves the current time of the time server via NTP and synchronizes its
internal time.