765-1103/100-000
Commissioning
Product manual | Version: 2.2.0
85
16DO FLD PN DC 24V 2.0A
Figure 29: Add Server Dialog – Advanced Tab
4. In the
Configuration Name
field, enter a name for your configuration, e.g. “Test.”
5. Select the
Advanced
tab.
6. In the
Server Information
section of the
Advanced
tab, enter the following informa-
tion in the
Endpoint URL
field:
opc.tcp://<IP address>:4840
. For
<IP ad-
dress>
, use the module’s IP address.
7. In the
Authentication Settings
section, select the
Username/Password
option for
write access to the module or
Anonymous
for read access.
8. If you selected the
Username/Password
option, enter your username and, if appli-
cable, password there.