765-1103/100-000
Commissioning
78
Product manual | Version: 2.2.0
16DO FLD PN DC 24V 2.0A
Table 42: Port-Specific Configuration Parameters
Node Name
Node Class
Access Default Description
OverCurrentPin1
Variable
Read
0
Warning level for current upper limit on pin 1;
unit: 1 mA
0: monitoring not enabled
OverCurrentPin2
Variable
Read
0
Warning level for current upper limit on pin 2;
unit: 1 mA
0: monitoring not enabled
OverCurrentPin4
Variable
Read
0
Warning level for current upper limit on pin 4;
unit: 1 mA
0: monitoring not enabled
UnderCurrentPin1
Variable
Read
0
Warning level for current lower limit on pin 1; unit:
1 mA
0: monitoring not enabled
UnderCurrentPin2
Variable
Read
0
Warning level for current lower limit on pin 2; unit:
1 mA
0: monitoring not enabled
UnderCurrentPin4
Variable
Read
0
Warning level for current lower limit on pin 4; unit:
1 mA
0: monitoring not enabled
10.3.3.1.4 Reading Port Process Values
The OPC UA server provides nodes with process data. For example, the OPC UA client
can read out the value on pin 4 of a port in the
Pin4ProcessData
node.
Process Data of the Digital Inputs and Outputs
The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector >
PortXX > SIOProcessData
Note
OPC UA client can only read process output data
The process output data is written by the PROFINET IO-Controller. The OPC UA client
can only read process output data.
The following table lists port-specific process data of the digital inputs and outputs.
Table 43: Port-Specific Process Data of the Digital Inputs and Outputs
Node Name
Node Class
Access
Description
Pin2ProcessData
Variable
Read
Process data on pin 2
Pin4ProcessData
Variable
Read
Process data on pin 4