Fieldbus Communication
•
189
EtherNet/IP (Ethernet/Industrial Protocol)
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
4.3.3.2.8 TCP/IP Interface (F5
hex
)
Class
Attribute ID Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2 Get
Max
Instance
UINT
Max. number of instances
3 Get
Num
Instances
UINT
Number of the current instanced
connections
Instance 1
Attribute ID Access NV
Name
Data type Description Default
value
1 Get
V
Status
DWORD
Interface
state
-
2 Get
V
Configurat
ion
Capability
DWORD
Inferface flags for possible kinds
of configuration
0x00000007
3 Set
NV
Configurat
ion
Control
DWORD
Specifies, how the device gets ist
TCP/IP configuration after the
first Power On
0x00000011
Physical
Link
Object
STRUCT of
Path size
UINT
Size of the path
0x0004
UINT
Number of 16 Bit words in the
following path
0x0002
4 Get
V
Path
Padded
EPATH
Logical path, which points to the
physical Link object
0x20 0xF6
0x24 0x01
Interface
Configurat
ion
STRUCT of
IP Address
UDINT
IP address
0
Network
Mask
UDINT
Net work mask
0
Gateway
Address
UDINT
IP address of default gateway
0
Name
Server
UDINT
IP address of the primary name of
the server
0
Name
Server 2
UDINT
IP address of the secundary name
of the server
0
5 Get
NV
Domain
Name
STRING
Default Domain name
“”
6 Set
NV
Host
Name
STRING
Device name
local host
Common Services
Service available
Service code
Class Instance
Service Name
Description
01 hex
yes
yes
Get_Attribute_All
Supplies contents of all attributes
0E hex
yes
yes
Get_Attribute_Sing
le
Supplies contents of the appropriate attribute
10 hex
no
yes
Set_Attribute_Singl
e
Modifies an attribute value