12 •
Technical Data
Technical Condition of the Devices
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
Range of
application
Required specification
emission of interference
Required specification
immunity to interference
Industrial areas
EN 61000-6-4 (2001)
EN 61000-6-2 (2001)
Residential areas
EN 61000-6-3 (2001)*)
EN 61000-6-1 (2001)
*)
The system meets the requirements on emission of interference in residential areas with
the field bus coupler/controller for:
ETHERNET
LonWorks
CANopen
DeviceNet
MODBUS
750-342/-841/-842/-860
750-319/-819
750-337/-837
750-306/-806
750-312/-314/ -315/ -316
750-812/-814/ -815/ -816
With a special permit, the system can also be implemented with other field bus
couplers/controllers in residential areas (housing, commercial and business areas, small-
scale enterprises). The special permit can be obtained from an authority or inspection
office. In Germany, the Federal Office for Post and Telecommunications and its branch
offices issues the permit.
It is possible to use other field bus couplers/controllers under certain boundary
conditions. Please contact WAGO Kontakttechnik GmbH & Co. KG.
Maximum power dissipation of the components
Bus modules
0.8 W / bus terminal (total power dissipation,
system/field)
Field bus coupler/controller
2.0 W / coupler/controller
Warning
The power dissipation of all installed components must not exceed the
maximum conductible power of the housing (cabinet).
When dimensioning the housing, care is to be taken that even under high
external temperatures, the temperature inside the housing does not exceed the
permissible ambient temperature of 55 °C.