196
•
EtherNet/IP (Ethernet/Industrial Protocol)
Object
model
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
Instance 1..255 (1. to 255. Input variable)
Attribute ID
Access
Name
Data type Description
Default
value
1 Set
Fb_In_Var
USINT
Fieldbus Input variable of the
PLC
0
This instance corresponds to the PFC’s input variables located at address
%IB2552-%IB2807 in a WAGO-I/O-PRO application.
Common Services
Service available
Service code
Class Instance
Service Name
Description
0E hex
yes
yes
Get_Attribute_Single Supplies contents of the appropriate attribute
10 hex
no
yes
Set_Attribute_Single
Modifies an attribute value
4.3.3.2.22
Input fieldbus variable USINT Extended 1 (A1
hex
)
Same as the Input Fieldbus Variable USINT Class (A0
hex
), however this
contains the PLC input variables 256..510.
This instance corresponds to the PFC’s input variables located at address
%IB2808-%IB3061 in a WAGO-I/O-PRO application.
4.3.3.2.23
Input fieldbus variable USINT Extended 2 (A2
hex
)
Same as the Input Fieldbus Variable USINT Class (A0
hex
), however this
contains the PLC input variables 511..512.
This instance corresponds to the PFC’s input variables located at address
%IB3062-%IB3063 in a WAGO-I/O-PRO application.
Class attribute max. Instance = 2
4.3.3.2.24
Output fieldbus variable USINT (A3
hex
)
Class
Attribute ID Access
Name
Data type Description
Default
value
1
Get
Revision
UINT
Revision of this object
1 (0x0001)
2 Get
Max
Instance
UINT
Max. number of instances
255 (0x0FF)
Instance 1..255 (1. to 255. Output variable)
Attribute ID Access
Name
Data type Description
Default
value
1 Get
Fb_Out_Var
USINT
Fieldbus Output variable of
the PLC
0
This instance corresponds to the PFC’s output variables located at address
%QB2552-%QB2807 in a WAGO-I/O-PRO application.