Fieldbus Controller • 87
Fieldbus Controller 750-872/020-000
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
3.1.8.4 IEC 61131-3-Program transfer
Transferring an IEC 61131-3 application program from your PC to the PFC
can be done in two different ways:
•
via the serial RS232 interface
•
via the fieldbus with TCP/IP.
Note
When choosing the driver, make sure the communication parameters are
correctly set and match your controller.
The
Communication parameters
dialog window is displayed through the
program menu item
Online
and then
Communication parameters
.
1. If you choose the RS232 driver, verify that the
Communication parameters
dialog window contains the following setup data: Baudrate=19200,
Parity=Even, Stop bits=1, Motorola byteorder=No.
2. If you choose the TCP/IP driver, verify that the
Communication parameters
dialog window contains the following setup data: Port=2455, Motorola
byteorder=No. Additionally, verify that the entered IP address is correct.
More information
For information on the installation of the communication drivers, as well as
details regarding the use of the software, please refer to the WAGO-I/O-
PRO
CAA
manual. An electronic copy of this manual can be found on WAGO’s
web site: