222
•
Process Data Architecture for MODBUS/TCP
Specialty
Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
Serial Interface Modules with Standard Data Format
750-650/000-001, -014, -015, -016
750-651/000-001
750-653/000-001, -006
The above Serial Interface Modules with Standard Data Format have a total of
6 bytes of user data in both the Input and Output Process Image (5 bytes of
serial data and 1 byte of control/status). The following table illustrates the
Input and Output Process Image, which have a total of 3 words mapped into
each image. Word alignment is applied.
Input and Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
D0
C/S
Data byte
Control/Status byte
1 D2
D1
2 D4
D3
Data bytes
Data Exchange Module
750-654, (and the variation /000-001)
The Data Exchange modules have a total of 4 bytes of user data in both the
Input and Output Process Image. The following tables illustrate the Input and
Output Process Image, which has a total of 2 words mapped into each image.
Word alignment is applied.
Input and Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 D1
D0
1 D3
D2
Data bytes