Fieldbus Controller • 111
Fieldbus Controller 750-872/020-000
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
2
I/O module(s) with unsupported
data type
Detect faulty I/O module as
follows: turn off the power supply.
Place the end module in the middle
of the fieldbus node. Turn the
power supply on again.
– If the LED is still blinking, turn
off the power supply and place the
end module in the middle of the
first half of the node (towards the
coupler).
– If the LED doesn’t blink, turn off
the power supply and place the end
module in the middle of the second
half of the node (away from the
coupler).
Turn the power supply on again.
Repeat this procedure until the
faulty I/O module is detected.
Replace the faulty I/O module.
Ask about a firmware update for
the fieldbus coupler.
3 Invalid
fieldbus
coupler/controller parameter
checksum
Turn off the power supply of the
node, reduce number of I/O
modules and turn the power supply
on again
4
Error occurred when writing to
serial EEPROM
Turn off the power supply of the
node, exchange fieldbus coupler
and turn the power supply on
again.
5
Error occurred with read access
to serial EEPROM
Turn off the power supply of the
node, exchange fieldbus coupler
and turn the power supply on
again.
6
Changed I/O module
configuration determined after
AUTORESET
Restart the fieldbus coupler by
turning the power supply off and
on again.
7
Firmware does not run on
existing hardware
Turn off the power supply of the
node, exchange fieldbus coupler
and turn the power supply on
again.
8
Time limit exceeded for
accessing the serial EEPROM
Turn off the power supply of the
node, exchange fieldbus coupler
and turn the power supply on
again.
9
Bus Coupler initialisation fault
Turn off the power supply of the
node, exchange fieldbus coupler
and turn the power supply on
again.
10
RTC-Powerfail
Adjust the clock and keep upright
the supply voltage of the bus
coupler for at least 15 minutes for
loading of the Goldcaps.