background image

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 1

Version: 4.0

I0000484

FIGURE 1: 

DIMENSIONS

INTERFACE SERIES

Installation & Operation Instructions

PTP

Phone:

 1-888-967-5224

Website:

 workaci.com

GENERAL INFORMATION

Two models of the PTP accept either a 3 to 15 or 3 

to 30 psig pneumatic pressure input and convert 

it to one of four proportional analog output 

ranges of 1-5, 2-10, 3-15 VDC or 4-20 mA which are 

jumper shunt selectable. A plugged gauge port is 

provided in the aluminum manifold for local 

mechanical indication via an optional 0 to 30 psi 

gauge. Custom calibration is available upon 

request for an additional charge. This will speed 

up installation time for the end user. 

MOUNTING INSTRUCTIONS

Circuit board may be mounted in any position. If 

circuit board slides out of snap track, a 

non-conductive “stop” may be required. Use only 

fingers to remove board from snap track. Slide 

out of snap track or push against side of snap 

track and lift that side of the circuit board to 

remove. 

Do not flex board or use tools.

WIRING INSTRUCTIONS

PRECAUTIONS

•  Remove power before wiring. Never 

connect or disconnect wiring with power 

applied.

•    When using a shielded cable, ground the 

shield only at the controller end. Grounding 

both ends can cause a ground loop. 

•   It is recommended you use an isolated 

UL-listed class 2 transformer when powering 

the unit with 24 VAC. Failure to wire the 

devices with the correct polarity when 

sharing transformers may result in damage 

to any device powered by the shared 

transformer.

•    If the 24 VDC or 24VAC power is shared 

with devices that have coils such as relays, 

solenoids, or other inductors,  each coil must 

have an MOV, DC/AC Transorb, Transient 

Voltage Suppressor (ACI Part: 142583), or 

diode placed across the coil or inductor. The 

cathode, or banded side of the DC Transorb 

or diode, connects to the positive side of the 

power supply. Without these snubbers, coils 

produce very large voltage spikes when 

de-energizing that can cause malfunction or 

destruction of electronic circuits.

•    All wiring must comply with all local and 

National Electric Codes.

3.25” (82.55mm)

2.18”

(55.49mm)

0.70” 

(17.78mm)

2.18”

(55.37mm)

3.88” (98.55mm)

PTP

PTP With Gauge

2.30” (58.42mm)

3.63”

(92.13mm)

2.95” (74.93mm)

Ø1.64”

(41.66mm)

Содержание PTP

Страница 1: ...it board to remove Do not flex board or use tools WIRING INSTRUCTIONS PRECAUTIONS Remove power before wiring Never connect or disconnect wiring with power applied When using a shielded cable ground the shield only at the controller end Grounding both ends can cause a ground loop It is recommended you use an isolated UL listed class 2 transformer when powering the unit with 24 VAC Failure to wire t...

Страница 2: ... manifold and pressure transducer is a pressure seal Do NOT stress the circuit board or allow the manifold to move Hold the manifold in one hand while installing pneumatic tubing onto the fitting and use care when removing tubing to avoid damaging fitting or moving manifold SETUP With power off select jumper position on jumper block J5 corresponding to the output required see Figure 3 CHECKOUT App...

Страница 3: ...perature 3 full scale across operating temperature range Furnished with integral in barb 80 100 micron filter Part PN004 90 Pluggable Screw Terminal Blocks 16 1 31 mm2 to 26 AWG 0 129 mm2 0 5 Nm Minimum 0 6 Nm Maximum 1 4 O D nominal 1 8 I D polyethylene Removeable brass barbed fitting in machined aluminum manifold Plugged 1 8 27 FNPT gauge port Gauge installed at additional cost 0 30 psig 0 200 k...

Страница 4: ...nents Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 4 0 I0000484 ...

Отзывы: