64 Commissioning
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
Table 40: "General" Parameters
Selection Field
Settings
Number format
There are two ways the process image can be
represented on the fieldbus:
Two's complement*
Amount/sign
Siemens S5 format
This can be used to fade in status indicators in the lowest
three bits.
On Bit 0 = Overrun
Bit 1 = Error
Bits 0 and 1 are set for wire breaks / overloads and
measurement over- and underranges (when the
corresponding channel diagnostics is set).
Bit 2 = Always 0
Off* No display of status indicators
Input filter frequency
The input filter is used to suppress interfering mains
frequency signal components. The frequency depends on
the application location and can be set with module
granularity.
50 Hz* The mains frequency is 50 Hz (e.g., Europe).
60 Hz The mains frequency is 60 Hz (e.g., USA).
* Default setting
The settings are transmitted to the I/O module using the
[Write]
button.
Save settings!
Click the [
Write
] button to transmit any settings that have been made to the I/O
module!
No Manufacturer Scaling in Siemens S5 Format!
If Siemens S5 format is switched on, the manufacturer scaling setting (see
Section “Scaling”) is not taken into account!