48 Process Image
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
Table 33: Signal Types “±10 V”, “±200 mV” “±20 mA”, Amount/sign format with Status Information in
the Process Image
Measuring range
Process value
Status
byte
hex.
Error
LED
± 10 V ± 200 mV ± 20 mA
Binary
Hex.
Dec.
Measuring value XFÜ
1)
n.a.
n.a.
< −
22.0
1111.1111.1111.1 011 0xFFFB
−
32763 0x50
on
Neg. sensor overload
3)
< −
10.4
< −
210.0
< −
21.0
1111.1111.1111.1 011 0xFFFB
−
32763 0x41
on
Underrange
2)
−
10.0
−
200.0
−
20.0
1111.1111.1111.1 000 0xFFF8
−
32760 0x00
off
−
6.0
−
120.0
−
12.0
1100.1100.1100.1 000 0xCCC8
−
19656 0x00
off
−
2.0
−
40.0
−
4.0
1001.1001.1001.1 000 0x9998
−
6552
0x00
off
0.0
0.0
0.0
0000.0000.0000.0 000 0x0000
0
0x00
off
2.0
40.0
4.0
0001.1001.1001.1 000 0x1998
6552
0x00
off
6.0
120.0
12.0
0100.1100.1100.1 000 0x4CC8 19656
0x00
off
10.0
200.0
20.0
0111.1111.1111.1 000 0x7FF8
32760
0x00
off
Exceeding
2)
0111.1111.1111.1 011 0x7FFB 32763
0x42
on
> 10.4
> 210.0
> 21.0
Sensor overload
3)
0111.1111.1111.1 011 0x7FFB 32763
0x50
on
n.a.
n.a.
> 22.0
1)
Status bits: X: not used, F= error, Ü= overrange
2)
When underrange / overrange limit is ON
3)
When wire break / overload diagnostics is ON