46 Process Image
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
4.3.1.2 Signal Types “±10 V”, “±200 mV” “±20 mA”, Two’s complement
(Default)
Only one signal type per channel can be set as operating mode via the
commissioning tool.
Table 30: Signal Types “±10 V”, “±200 mV”, “±20 mA”, Two’s Complement
Measuring range
Process value
Status
byte hex.
Error
LED
±10 V
±200 mV ±20 mA
Binary
Hex.
Dec.
n.a.
n.a.
< −
22.0
1000.0000.0000.0000 0x8000
−
32768
0x50
on
Neg. sensor overload
2)
< −
10.4
< −
210.0
< −
21.0
1000.0000.0000.0000 0x8000
−
32768
0x41
on
Underrange
1)
−
10.0
−
200.0
−
20.0 1000.0000.0000.0000 0x8000
−
32768
0x00
off
−
6.0
−
120.0
−
12.0 1011.0011.0011.0011 0xB333
−
19661
0x00
off
−
2.0
−
40.0
−
4.0 1110.0110.0110.0110 0xE666
−
6554
0x00
off
0.0
0.0
0.0
0000.0000.0000.0000 0x0000
0
0x00
off
2.0
40.0
4.0
0001.1001.1001.1001 0x1999
6553
0x00
off
6.0
120.0
12.0
0100.1100.1100.1100 0x4CCC 19660
0x00
off
10.0
200.0
20.0 0111.1111.1111.1111 0x7FFF 32767
0x00
off
Exceeding
1)
0111.1111.1111.1111 0x7FFF
32767
0x42
on
> 10.4
> 210.0
> 21.0
Sensor overload
2)
0111.1111.1111.1111 0x7FFF
32767
0x50
on
n.a.
n.a.
> 22.0
1)
When underrange / overrange limit is ON
2)
When wire break / overload diagnostics is ON