WAGO I/O System 750 XTR
Commissioning 73
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
7.2.2.1 All PROFIBUS DP and PROFINET IO Fieldbus Couplers/Controllers
The following assignment applies to the parameters of the I/O module when
using PROFIBUS DP and PROFINET IO fieldbus devices.
Table 45: Specific Module/Channel Parameters for 750-471/040-000
GSD file
WAGO-I/O-
CHECK
Parameter
Value
Checkbox
Value
Number format
Twos Complement
*)
Number format
Twos Complement
*)
Sign magnitude
Sign magnitude
Siemens
S5 format
disabled
*)
Siemens
S5 format
Off
*)
activated
On
Input filter frequency
50 Hz
*)
Input filter frequency
50 Hz
*)
60 Hz
60 Hz
Signal type Channel x
(x = 0…3)
disabled
Signal type
Channel disabled
0-10 V
0-10 V
+/−
10 V
+/
−
10 V
0-20 mA
0-20 mA
4-20 mA
*)
4-20 mA
*)
3,6-21,0 mA
(Namur NE43)
3,6-21,0 mA
(Namur NE43)
+/−
20 mA
+/−
20 mA
+/−
200 mV
+/−
200 mV
Input filter
Channel x
(x = 0…3)
disabled
*)
Input filter
Off
*)
activated
On
User scaling
1)
disabled
*)
User scaling
Checkbox
disabled
*)
activated
Checkbox
activated
Offset
1)
−
32768 … 0
*)
… 32767 Offset
−
32768 … 0
*)
… 32767
Gain
1)
−
32768 … 16384
*)
…
32767
Gain
−
2.0000 … 1.0000
*)
…
1.9999
2)
*)
Default setting
1)
only PROFINET IO couplers
2)
The resolution 1/16384 is already taken into account in WAGO-I/O-
CHECK
.