WAGO I/O System 750 XTR
Process Image 47
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
Table 31: Signal Types “±10 V”, “±200 mV” “±20 mA”, Two’s Complement with Status Information in
the Process Image
Measuring range
Process value
Status
byte
hex.
Error
LED
±10 V ±200 mV ±20 mA
Binary
Hex.
Dec.
Measuring value XFÜ
1)
n.a.
n.a.
< −
22.0
1000.0000.0000.0 011 0x8003
−
32765 0x50
on
Neg. sensor overload
3)
< −
10.4
< −
210.0
< −
21.0
1000.0000.0000.0 011 0x8003
−
32765 0x41
on
Underrange
2)
−
10.0
−
200.0
−
20.0
1000.0000.0000.0 000 0x8000
−
32768 0x00
off
−
6.0
−
120.0
−
12.0
1011.0011.0011.0 000 0xB330
−
19664 0x00
off
−
2.0
−
40.0
−
4.0
1110.0110.0110.0 000 0xE660
−
6560
0x00
off
0.0
0.0
0.0
0000.0000.0000.0 000 0x0000
0
0x00
off
2.0
40.0
4.0
0001.1001.1001.1 000 0x1998
6552
0x00
off
6.0
120.0
12.0
0100.1100.1100.1 000 0x4CC8 19656
0x00
off
10.0
200.0
20.0
0111.1111.1111.1 000 0x7FF8 32760
0x00
off
Exceeding
2)
0111.1111.1111.1 011 0x7FFB 32763
0x42
on
> 10.4 > 210.0
> 21.0
Sensor overload
3)
0111.1111.1111.1 011 0x7FFB 32763
0x50
on
n.a.
n.a.
> 22.0
1)
Status bits: X: not used, F= error, Ü= overrange
2)
When underrange / overrange limit is ON
3)
When wire break / overload diagnostics is ON
Table 32: Signal Types “±10 V”, “±200 mV” “±20 mA”, Amount/sign format
Measuring range
Process value
Status
byte hex.
Error
LED
±10 V ±200 mV ±20 mA
Binary
Hex.
Dec.
n.a.
n.a.
< −
22.0
1111.1111.1111.1111 0xFFFF
−
32767
0x50
on
Neg. sensor overload
2)
< −
10.4 <
−
210.0
< −
21.0
1111.1111.1111.1111 0xFFFF
−
32767
0x41
on
Unterschreitung
1)
−
10.0
−
200.0
−
20.0 1111.1111.1111.1111 0xFFFF
−
32767
0x00
off
−
6.0
−
120.0
−
12.0 1100.1100.1100.1100 0xCCCC
−
19660
0x00
off
−
2.0
−
40.0
−
4.0 1110.0110.0110.0110 0x9999
−
6553
0x00
off
0.0
0.0
0.0
0000.0000.0000.0000 0x0000
0
0x00
off
2.0
40.0
4.0
0001.1001.1001.1001 0x1999
6553
0x00
off
6.0
120.0
12.0
0100.1100.1100.1100 0x4CCC 19660
0x00
off
10.0
200.0
20.0 0111.1111.1111.1111 0x7FFF
32767
0x00
off
Exceeding
1)
0111.1111.1111.1111 0x7FFF
32767
0x42
on
> 10.4
> 210.0
> 21.0
Sensor overload
2)
0111.1111.1111.1111 0x7FFF
32767
0x50
on
n.a.
n.a.
> 22.0
1)
When underrange / overrange limit is ON
2)
When wire break / overload diagnostics is ON