WAGO I/O System 750 XTR
Process Image 51
750-471/040-000 4AI U/I Diff Galv XTR
Manual
Version 1.0.2
Table 36: Signal Type “Namur NE43”, Amount/sign format
Measuring range [mA]
Process value
Statusbyte
hex.
Error
LED
Namur NE43
Binary
Hex.
Dec.
<
−
14,0 mA
1000.0001.1000.1100
0x818C
−
397
0x50
on
Neg. sensor overload
3)
< 1,0
1000.0001.1000.1100
0x818C
−
397
0x60
on
Wire break or
Overload
2)
< 3,6
1000.0001.1000.1100
0x818C
−
397
0x41
on
Underrange
1)
3,8
1000.0001.1000.1100
0x818C
−
397
0x00
off
4,0
0000.0000.0000.0000
0x0000
0
0x00
off
5,6
0000.1100.0110.1001
0x0C69
3177
0x00
off
7,2
0001.1000.1100.1010
0x18CA
6346
0x00
off
8,8
0010.0101.0011.1100
0x253C
9532
0x00
off
10,4
0011.0001.1010.0110
0x31A6
12710
0x00
off
12,0
0011.1110.0000.1111
0x3E0F
15887
0x00
off
13,6
0100.1010.0111.1000
0x4A78
19064
0x00
off
15,2
0101.0110.1110.0010
0x56E2
22242
0x00
off
16,8
0110.0011.0100.1011
0x634B
25419
0x00
off
18,4
0110.1111.1011.0100
0x6FB4
28596
0x00
off
20,0
0111.1100.0001.1110
0x7C1E
31774
0x00
off
20,5
0111.1111.1111.1111
0x7FFF
32767
0x00
off
Exceeding
1)
0111.1111.1111.1111
0x7FFF
32767
0x42
on
> 21,0
Sensor overload
2)
0111.1111.1111.1111
0x7FFF
32767
0x50
on
> 22,0
1)
When underrange / overrange limit is ON
2)
When wire break / overload diagnostics is ON