Process Data Architecture for EtherNet/IP
Analog Output Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
5.3.4 Analog Output Modules
The hardware of an analog output module has 16 bits of measured analog data
per channel and 8 bits of control/status. However, the coupler/controller with
EtherNet/IP does not have access to the 8 control/status bits. Therefore, the
coupler/controller with EtherNet/IP can only access the 16 bits of analog data
per channel, which are grouped as words and mapped in Intel format in the
Output Process Image.
When digital output modules are also present in the node, the analog output
data is always mapped into the Output Process Image in front of the digital
data.
Each output channel seizes one Instance in the Analog Output Point Object
(Class 0x68).
2 Channel Analog Output Modules
750-550, -552, -554, -556, -560, -585, (and all variations),
753-550, -552, -554, -556
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
D1
D0
Output Value Channel 1
1
D3
D2
Output Value Channel 2
The output modules represent 2x2 bytes and seize 2 Instances in Class (0x68).
4 Channel Analog Output Modules
750-553, -555, -557, -559, 753-553, -555, -557, -559
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
D1
D0
Output Value Channel 1
1
D3
D2
Output Value Channel 2
2
D5
D4
Output Value Channel 3
3
D7
D6
Output Value Channel 4
The output modules represent 4x2 bytes and seize 4 Instances in Class (0x68).