88 •
Fieldbus Coupler
Fieldbus Coupler 750-341
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
3.1.11 Technical Data
System data
No. of nodes
limited by ETHERNET specification
Transmission medium
Twisted Pair S-UTP 100
Ω
cat. 5
Buscoupler connection
RJ45
Max. length of fieldbus segment
100 m between hub station and 750-341;
max. length of network limited by ETHERNET
specification
Baud rate
10/100 Mbit/s
Protocols MODBUS/TCP
(UDP), ETHERNET/IP, HTTP,
BootP, DHCP, DNS, SNTP, FTP, SNMP
Technical Data
No. of I/O modules
with bus extension
64
250
Fieldbus
Input process image max.
Output process image max.
2 kByte
2 kByte
Configuration via
PC
Max. no. of socket connections
3 HTTP, 15 MODBUS/TCP, 128 for Ethernet/IP
Voltage supply
DC 24 V (-25 % ... + 30 %)
Input current
max
500 mA at 24 V
Efficiency of the power supply
87 %
Internal current consumption
300 mA at 5 V
Total current for I/O modules
1700 mA at 5 V
Isolation
500 V system/supply
Voltage via power jumper contacts
DC 24 V (-25 % ... + 30 %)
Current via power jumper contacts
max
DC 10 A
Dimensions (mm) W x H x L
51 x 65* x 100 (*from upper edge of DIN 35 rail)
Weight
ca. 195 g
Accessories
Miniature WSB quick marking system
Standards and Regulations (cf. Chapter 2.2)
EMC CE-Immunity to interference
acc. to EN 50082-2 (96), EN 61000-6-2 (99)
EMC CE-Emission of interference
acc. to EN 50081-2 (94)
EMC marine applications-Immunity to
interference
acc. to Germanischer Lloyd (2001)
EMC marine applications-Emission of
interference
acc. to Germanischer Lloyd (2001)
Содержание 750-341
Страница 245: ...Notes 239 WAGO I O SYSTEM 750 ETHERNET TCP IP...