MODBUS Functions
MODBUS Register Mapping
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
4.2.4 MODBUS Register Mapping
The following tables display the MODBUS addressing and the corresponding
IEC61131 addressing for the process image and the internal variables is
represented.
Via the register services the states of the complex and digital I/O modules can
be determined or changed.
Register (Word) Access Reading (with FC3 and FC4):
Modbus-Address
IEC61131
[dec]
[hex]
Address
Memory Range
0
... 255
0x0000
... 0x00FF
%IW0
... %IW255
Physical Input Area (1)
First 256 Words of physical input data
256
... 511
0x0100
... 0x01FF
-
Modbus Exception:
“Illegal data address”
512
... 767
0x0200
... 0x02FF
%QW0
... %QW255
Physical Output Area (1)
First 256 Words of physical output data
768
... 4095
0x0300
... 0x0FFF
-
Modbus Exception: “
Illegal data address”
4096
... 12287
0x1000
... 0x2FFF
-
Configuration Register
(see following Chapter 4.2.5.3 Configuration
Functions)
12288
... 24575
0x3000
... 0x5FFF
-
Modbus Exception: “
Illegal data address”
24576
... 25340
0x6000
... 0x62FC
%IW256
... %IW1020
Physical Input Area (2)
Additional 764 Words physical input data
25341
... 28671
0x62FD
... 0x6FFF
-
Modbus Exception: “
Illegal data address”
28672
... 29436
0x7000
... 0x72FC
%QW256
... %QW1020
Physical Output Area (2)
Additional 764 Words physical output data
29437
... 65535
0x72FD
... 0xFFFF
-
Modbus Exception: “
Illegal data address”
Register (Word) Access Writing (with FC6 and FC16):
Modbus-Address
IEC61131
[dec]
[hex]
Address
Memory Range
0
... 255
0x0000
... 0x00FF
%QW0
... %QW255
Physical Output Area (1)
First 256 Words of physical output data
256
... 511
0x0100
... 0x01FF
-
Modbus Exception:
“Illegal data address”
512
... 767
0x0200
... 0x02FF
%QW0
... %QW255
Physical Output Area (1)
First 256 Words of physical output data
768
... 4095
0x0300
... 0x0FFF
-
Modbus Exception: “
Illegal data address”
4096
... 12287
0x1000
... 0x2FFF
-
Configuration Register
(see following Chapter 4.2.5.3 Configuration
Functions)
12288
... 24575
0x3000
... 0x5FFF
-
Modbus Exception: “
Illegal data address”
24576
0x6000
%QW256
Physical Output Area (2)