Process Data Architecture for MODBUS/TCP
Specialty
Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 - S
Status
byte
1 D1 D0
2 D3 D2
Counter Value
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 - C
Control
byte
1 D1 D0
2 D3 D2
Counter Setting Value
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the
Input and Output Process Image (4 bytes of counter data and 1 byte of
control/status). The two counter values are supplied as 16 bits. The following
tables illustrate the Input and Output Process Image, which has a total of 3
words mapped into each image. Word alignment is applied.
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 - S
Status
byte
1
D1
D0
Counter Value of Counter 1
2
D3
D2
Counter Value of Counter 2
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 - C
Control
byte
1 D1 D0
Counter
Setting Value of Counter 1
2 D3 D2
Counter
Setting Value of Counter 2