Process Data Architecture for EtherNet/IP
Specialty
Modules
WAGO-I/O-SYSTEM
750
ETHERNET TCP/IP
Incremental Encoder Interface Modules
750-631
The above Incremental Encoder Interface modules have 5 bytes of input data
and 3 bytes of output data. The following tables illustrate the Input and Output
Process Image, which have 4 words into each image. Word alignment is
applied.
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
S
not used
Status byte
1 D1
D0
Counter
word
2 -
-
not
used
3 D4
D3
Latch
word
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
C
not used
Control byte
1
D1
D0
Counter Setting word
2 -
-
not
used
3 -
-
not
used
And the specialty modules represent 1x6 bytes output data and seize 1
Instance in Class (0x68).
750-634
The above Incremental Encoder Interface module has 5 bytes of input data (6
bytes in cycle duration measurement mode) and 3 bytes of output data. The
following tables illustrate the Input and Output Process Image, which has 4
words mapped into each image. Word alignment is applied.
Input Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
S
not used
Status byte
1 D1 D0
Counter
word
2 -
(D2)*
)
not used
(Periodic time)
3 D4 D3
Latch
word
*
)
If cycle duration measurement mode is enabled in the control byte, the cycle
duration is given as a 24-bit value that is stored in D2 together with D3/D4.
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).