I/O Modules
•
205
Process Data Architecture for EtherNet/IP
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
C
not used
Control byte
1
D1
D0
Counter Setting word
2 - -
3 - -
not used
And the specialty modules represent 1x6 bytes output data and seize 1
Instance in Class (0x68).
750-637
The above Incremental Encoder Interface Module has a total of 6 bytes of user
data in both the Input and Output Process Image (4 bytes of encoder data and
2 bytes of control/status). The following table illustrates the Input and Output
Process Image, which have 4 words mapped into each image. Word alignment
is applied.
Input and Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0
-
C0/S0
Control/Status byte 1
1 D1 D0
Data
Value
2
-
C1/S1
Control/Status byte 2
3
D3
D2
Data Value
The specialty modules represent 2x3 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
750-635, 753-635
The above Digital Pulse Interface module has a total of 4 bytes of user data in
both the Input and Output Process Image (3 bytes of module data and 1 byte of
control/status). The following table illustrates the Input and Output Process
Image, which have 2 words mapped into each image. Word alignment is
applied.
Input and Output Process Image
Byte Destination
Offset
High Byte
Low Byte
Remark
0 D0 C0/S0 Data
byte
Control/Status
byte
1 D2 D1
Data
bytes
The specialty modules represent 1x4 bytes input and output data and seize 1
Instance in Class (0x67) and 1 Instance in Class (0x68).