Fieldbus
Communication
•
157
EtherNet/IP (Ethernet/Industrial Protocol)
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
Instance
Instance 1
Attribute ID Access
NV
Name
Data type Description Default
value
5 (0x05)
Get
V
ProcessState
USINT
State of coupler/
Error mask
Bit 0 Internal bus error
Bit 3 Module diagnostics
(0x08)
Bit 7 Fieldbus error (0x80)
0
6 (0x06)
Get
V
DNS_i_Trm
nldia
UINT
Module diagnostics
Bit 0..7:Module number
Bit 8..14:Module channel
Bit 15: 0/1 Error repair/arisen
0
7 (0x07)
Get
V
CnfLen.Anal
ogOut
UINT
Number of I/O bits for the
analog outputs
-
8 (0x08)
Get
V
CnfLen.Anal
ogInp
UINT
Number of I/O bits for the
analog inputs
-
9 (0x09)
Get
V
CnfLen.Digi
talOut
UINT
Number of I/O bits for the
digital outputs
-
10 (0x0A)
Get
V
CnfLen.Digi
talInp
UINT
Number of I/O bits for the
digital inputs
-
11 (0x0B)
Set
NV
Bk_Fault_R
eaction
USINT
Fieldbus error reaction
0:
stop local I/O cycles
1:
set all output to 0
2:
no error reaction
3:
no error reaction
1
12..26
(0x0C...0x1A)
Reserved for compatibility to DeviceNet
40..43
(0x28... 0x2B)
Reserved for compatibility to DeviceNet
45 (0x2D)
Get
V
Bk_Led_Err
_Code
UINT
I/O LED Error Code
0
46 (0x2E)
Get
V
Bk_Led_Err
_Arg
UINT
I/O LED Error Argument
0
120 (0x78)
Set
NV
Bk_HeaderC
fgOT
UINT
Indicates whether the
RUN/IDLE header is used
Originator -> Target direction
0
is used
1
is not used
0x0000
121 (0x79)
Set
NV
Bk_HeaderC
fgTO
UINT
Indicates whether the
RUN/IDLE header is used
Originator -> Target direction
0
is used
1
is not used
0x0001
Common Services
Service available
Service code
Class Instance
Service
Name
Description
0E hex
yes
yes
Get_Attribute_
Supplies contents of the appropriate attribute
Содержание 750-341
Страница 245: ...Notes 239 WAGO I O SYSTEM 750 ETHERNET TCP IP...