Design
TITANUS
MICRO·SENS
®
82
06/13
O not purposeful
If the blockage of 1 aspiration apertures out of a total of 6 aspiration aper-
tures is recognised, then with the aid of the diagnostics tool, air flow monitor-
ing can be set to ±10 %.
NOTICE
For a project planning according to EN 54-20 or ISO 7240-20, the air flow
monitoring has to be adjusted to ≤20 % in either case.
Doppel-U-Pipe system
Figure 46: Double-U-Pipe system for area protection
min. distance TITANUS
®
– T-no.
2 m
max. distance TITANUS
®
– T-no.
20 m
max. branch length
12.5 m
max. overall pipe length per pipe system
pipe
∅
25 mm plus
pipe
∅
12 mm
50 m
8 x 3 m
max. overall pipe length per pipe system per
with high fan voltage 9,0 V
pipe
∅
25 mm plus
pipe
∅
12 mm
40 m
8 x 3m
min. distance between 2 aspiration apertures (d)
4 m
max. distance between 2 aspiration apertures (d)
10 m
max. number aspiration apertures (n) per pipe system
8 no.
Example
5.3.1.4
1 Pipe system
Limit values
Содержание Titanus Micro-Sens
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 16: ......
Страница 24: ......
Страница 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Страница 100: ......
Страница 140: ......
Страница 148: ...Installation Pipe System TITANUS MICRO SENS 148 06 13 Figure 91 Attaching the aspiration reducing film sheet ...
Страница 164: ......
Страница 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Страница 186: ......
Страница 202: ......
Страница 203: ...Appendix Projection Tables System Product List Inspection Protocol Glossary Conformity certification pursuant to EU ...
Страница 204: ......
Страница 210: ......
Страница 226: ......
Страница 228: ......
Страница 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Страница 235: ......
Страница 236: ......
Страница 237: ...TITANUS MICRO SENS 06 13 ...
Страница 238: ...TITANUS MICRO SENS ...