Maintenance
TITANUS
MICRO·SENS
®
200
06/13
Testing fire seat location and the reaction
indicators
Testing fire seat location and the reaction indicators.
At the first location screen “ROOM·IDENT“ (see figure in chapter Commis-
sioning „Localisation of the fire location“) the button “Test” needs to be
prened in order to open this screen. To test, select the “Pre selection time”
and then click on Start to deter-mine the seat of fire.
The TITANUS
MICRO·SENS
®
switches to blowing out the aspiration pipe.
The particular aspiration point must be charged with smoke until the pre-
selected time has elapsed. There must still be smoke at the aspiration point
for 10 to 15 seconds after the pre-selected time has expired.
After the pre-selected time has elapsed, the TITANUS
MICRO·SENS
®
switches to aspiration and the time measured until the smoke is detected de-
termines the aspiration point. Check whether it is the right aspiration point.
9.10
Содержание Titanus Micro-Sens
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 16: ......
Страница 24: ......
Страница 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Страница 100: ......
Страница 140: ......
Страница 148: ...Installation Pipe System TITANUS MICRO SENS 148 06 13 Figure 91 Attaching the aspiration reducing film sheet ...
Страница 164: ......
Страница 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Страница 186: ......
Страница 202: ......
Страница 203: ...Appendix Projection Tables System Product List Inspection Protocol Glossary Conformity certification pursuant to EU ...
Страница 204: ......
Страница 210: ......
Страница 226: ......
Страница 228: ......
Страница 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Страница 235: ......
Страница 236: ......
Страница 237: ...TITANUS MICRO SENS 06 13 ...
Страница 238: ...TITANUS MICRO SENS ...