Installation
06/13
133
Figure 87: Height, Air Pressure and Fan Voltage settings
In the diagnostic software, the current TITANUS
MICRO·SENS
®
figures are
displayed on the Settings screen.
The figures can be changed by pressing the Settings button.
Setting reaction sensitivity
The sensitivity (fire alarm) of the detection unit can be set using the TITA-
NUS
MICRO·SENS
®
diagnostic tool.
Sensitivity
Sensitivity
Standard
Settings
stages
Detection Unit
DM-TM-10
0.1 - 2 %/m
0.1 %/m
0.1 %/m
Detection Unit
DM-TM-50
0.5 - 2 %/m
0.5 %/m
0.1 %/m
6.12.1.1
Содержание Titanus Micro-Sens
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 16: ......
Страница 24: ......
Страница 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Страница 100: ......
Страница 140: ......
Страница 148: ...Installation Pipe System TITANUS MICRO SENS 148 06 13 Figure 91 Attaching the aspiration reducing film sheet ...
Страница 164: ......
Страница 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Страница 186: ......
Страница 202: ......
Страница 203: ...Appendix Projection Tables System Product List Inspection Protocol Glossary Conformity certification pursuant to EU ...
Страница 204: ......
Страница 210: ......
Страница 226: ......
Страница 228: ......
Страница 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Страница 235: ......
Страница 236: ......
Страница 237: ...TITANUS MICRO SENS 06 13 ...
Страница 238: ...TITANUS MICRO SENS ...