Commissioning
TITANUS
MICRO·SENS
®
182
06/13
First the number of aspiration apertures then the blow through time and blow
through and aspiration fan voltage must be entered.
Click on the question mark for help.
? Blow through time help
Blow through time (for blow through fan voltage 13.5 V)
During blow through time the smoke is blown backwards out of the pipe. The
blow through time can be selected from the following table (intermediate val-
ues = next largest value):
Pipe Length (m)
Time (secs)
10 80
15 97
20 113
25 130
30 147
35 163
40 180
1 second should be added to the blow through time for each pipe bend or
angle.
Содержание Titanus Micro-Sens
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 16: ......
Страница 24: ......
Страница 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Страница 100: ......
Страница 140: ......
Страница 148: ...Installation Pipe System TITANUS MICRO SENS 148 06 13 Figure 91 Attaching the aspiration reducing film sheet ...
Страница 164: ......
Страница 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Страница 186: ......
Страница 202: ......
Страница 203: ...Appendix Projection Tables System Product List Inspection Protocol Glossary Conformity certification pursuant to EU ...
Страница 204: ......
Страница 210: ......
Страница 226: ......
Страница 228: ......
Страница 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Страница 235: ......
Страница 236: ......
Страница 237: ...TITANUS MICRO SENS 06 13 ...
Страница 238: ...TITANUS MICRO SENS ...