Installation
TITANUS
MICRO·SENS
®
114
06/13
Incorporating the reset and isolating button
board
If a reset or isolating button is needed, the plate must be fitted into an addi-
tional housing.
Figure 70: Incorporating the reset and isolating board into the housing
Proceed as follows to incorporate the reset and isolating button board:
1. Using a screwdriver, loosen the four screws on the additional housing
cover.
2. Push the spacer blocks into the installation board (for fixing points see
Figure "Arrangement of holes on the installation plate of the additional
housing") on the additional housing. The reset and isolating button board
is then engaged with the spacer blocks using the holes provided.
3. Feed the wires through as per the following switching plan.
4. Fit the cover again, using a screwdriver to fit the four screws on the de-
vice cover firmly.
6.6
Fitting
Содержание Titanus Micro-Sens
Страница 1: ...Air sampling smoke detection system Fire Detection TITANUS MICRO SENS Technical Manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 16: ......
Страница 24: ......
Страница 74: ...Design TITANUS MICRO SENS 74 06 13 ...
Страница 100: ......
Страница 140: ......
Страница 148: ...Installation Pipe System TITANUS MICRO SENS 148 06 13 Figure 91 Attaching the aspiration reducing film sheet ...
Страница 164: ......
Страница 177: ...TITANUS MICRO SENS Commissioning 06 13 177 ...
Страница 186: ......
Страница 202: ......
Страница 203: ...Appendix Projection Tables System Product List Inspection Protocol Glossary Conformity certification pursuant to EU ...
Страница 204: ......
Страница 210: ......
Страница 226: ......
Страница 228: ......
Страница 234: ...TITANUS MICRO SENS Glossary TMS_A_Glossar e DOC Data 01 09 ...
Страница 235: ......
Страница 236: ......
Страница 237: ...TITANUS MICRO SENS 06 13 ...
Страница 238: ...TITANUS MICRO SENS ...