May 2, 2011
WIRING DETAILS
Contact Inputs
24
Part Number 11694 Rev 1.6
JACE-700
MOUNTING AND WIRING GUIDE
|
Contact Inputs
Three contact inputs (CIs) are on a 6-position connector next to the 2-position
external battery connector. CIs typically monitor normally-closed (N.C.) alarm
contacts, if available on a UPS and/or the “door tamper” switch of a nearby
enclosure. These CIs are
unsupervised
—no end-of-line resistors are required.
on page 24 shows example wiring to all three CIs of the controller.
Figure 10 Contact Input wiring to JACE-700 controller.
External 12V Backup Battery
A 2-position connector provides support for an external 12V sealed lead-acid (SLA)
type rechargable battery. For more details, see
Figure 11 Sealed lead-acid backup battery connection on JACE-700 controller.
Note
The minimum wire size for battery connections is 18AWG (1.0mm
2
) for
up to 4 ft. (1.22m), or 16AWG (1.29mm
2
) for up to 12 ft. (3.66m).