10
4. ASSEMBLY
NOTE
Installation location should be suitably selected with special consideration of potential loads and vibrations.
Prior to any installation or maintenance works, disconnect the device from the power supply and secure it against accidental power-up.
aulic lines (especially supply lines) to the device, you should clean/rinse the installation by draining two litres out of it.
NOTE
It is necessary to maintain a minimum distance of 0.4m from the wall or the ceiling; otherwise the device can malfunction, the fan can be damaged or its operating noise can increase.
If the device will be installed on a wall or under a ceiling, observe the following factors:
mounting height
OPT
. 2-5m (V
olcano V mini)
OPT
. 2,5-8m (V
olcano VR1, VR2, VR3)
OPT
. 3-8m (V
olcano V mini)
OPT
. 3-1
1m (V
olcano VR1, VR2)
OPT
. 3-12m (V
olcano VR3)
OPT
. 6-15m (V
olcano VR-D)
* for vertical air guides adjustment
distance between units – recommended distance 6-12m (Volcano VR1, VR2, VR3), 3-7m (Volcano VR Mini), in order to ensure even hot air diffusion
range of air stream
Max. 14m* (Volcano V mini)
Max. 22m* (Volcano VR1, VR2)
Max. 25m* (Volcano VR3)
Max. 28m* (Volcano VR-D)
Max. 2m** (Volcano V mini)
Max. 13m* (Volcano VR1, VR2)
Max. 15m* (Volcano VR3, VR-D)
* for horizontal air guide adjustment
** for symmetric air guide adjustment at an angle of 45°
device noise level (depending on acoustic characteristics of a room)
operation mode of the heating device, e.g. it can also operate as an air mixing device preventing air stratification
direction of air distribution should be controlled in a way that prevents draughts. Air stream must not be directed at walls, brackets, girders, cranes, shelves, machines, etc.
OPT. 3-7m
(Volcano VR Mini)
OPT. 6-12m
(Volcano VR1, VR2, VR3)
OPT
. 2-5m (V
olcano VR Mini)
OPT
. 2,5-8m (V
olcano VR1, VR2, VR3)
29