6
alarm.
03
START
Red
The indicator light will be lit if the system has sent out a
linkage request of a certain module.
04
FEEDBACK
Red
The indicator light will be lit if the system has received a
linkage feedback of a certain module.
05
FAULT
Yellow
The indicator light will be lit when the system detects any fault
alarm (regardless of fault types).
06
SYSTEM
FAULT
Yellow
The indicator light will be lit when the machine is in fault or the
system is not operating as expected.
07
DELAY
Red
When the fire alarm triggers the linkage, the indicator light will
be lit during the delay time and will go off after the linkage
delay expires and the linkage has been achieved.
08
POWER
FAULT
Yellow
The indicator light will be lit when the system detects the alarm
of host power supply (regardless of fault type). The power fault
may cause the overall system not to function correctly and
thus the indicator light is equipped specially.
09
SOUNDER
FAULT
Yellow
The indicator light will be lit when the acousto-optic alarm
apparatus or far sound equipment (alarm bell) in the system
goes wrong.
10
SELF -TEST
Yellow
The indicator light will be lit when the machine carries out
self-test or single-point test and will go off after self-test
completion.
Key functional zone:
Figure 3-3 Key function zone
1)
LOGIN
function key (with light key)
Originally, the panel keys are under OFF state at power-on,
AND
LOGIN indicator light is off.
Press LOGIN key or * key of panel keyboard or C
TRL
+A
LT
+D
EL
of USB keyboard and the
password input box will prompt on the display, then enter into the password and login in (see
User’s Manual for details). The system will open the panel keyboard when receiving the