13
• The appliance must expel air directly to the outside through a single dedicated duct.
• The flow of extracted air must be clean (i.e. free of grease, soot, chemical and corrosive agents and explosive or
flammable mixtures).
• Keep the air intake and outlet ports of the appliance free of obstructions, to ensure optimum air flow.
• Maximum operating temperature: 45°C.
• Specifications for the power supply must correspond to the electrical data on ID plate A (Fig. 1).
• The appliance must be installed by a professionally qualified technician.
• The appliance must be wired to the power supply by way of a multi-pole isolating switch with a gap
of at least 3 mm between contacts.
Items supplied
- Full recovery unit with fans installed inside the unit ;
- Countercurrent heat exchanger in polypropylene pre-inserted inside the unit;
- N°2 F7 class filters pre-inserted inside the unit;
- Electrical box with predisposition connection terminal;
- Wall mounting bracket
Air connections meaning
: (Fig.A)
(A)
Clean air outlet inside the room
(B)
Stale air outlet to outside
(C)
Stale air intake from room
(D)
Fresh air intake from outside
Installation
The unit must be installed according to national and local rules governing the use of electrical devices and according to
the following guidelines: install the unit within residential buildings with ambient temperature between 0 ° C and 45 ° C;
avoid areas in close proximity to sources of heat, steam, flammable and / or explosive and particularly dusty areas; install
the unit in a place not subject to frost (the condensation water must be discharged not frozen, at a certain inclination,
using a siphon); not install the unit in areas with a high relative humidity (such as the bathroom or toilet) to avoid conden-
sation on the outer surface; choose an installation place where there is enough space around the unit for the air ducts and
connections in order to perform maintenance; the consistency of the ceiling / wall / floor where the unit will be installed
must be adapted to the weight of the unit and does not cause vibrations.
Unit positioning:
Wall mounting (Fig.1-4)
NOTA:
Ensure sufficient space for the performance of maintenance tasks: it must be guaranteed the opening of the unit's
front panel. Do not mount the unit with the hips in direct contact with the walls to avoid possible noises from contact, insert
strips of rubber or neoprene in this case.
- Verify the minimum distance to the floor: the space must be enought to correclty mount condensate drain siphons (see
paragraph: “Drain connection”).
- Position the wall bracket on the wall and mark (on wall) holes positions using a pencil.Verify vertical and horizontal ali-
gnment between holes.
- Make holes for wall fixing , fix the wall bracket using suitable fixing methos and equipment.
- Position the unit above the bracket and adjust the two spacers to ensure a correct support on the vertical surface.
Floor mounting
It is possible to mount the appliance on the floor using the optional floor support accessory ( MP Cod. 21605 ) , for in-
structions about installation of the accessory please refer to the respective manual.