Connecting the condensate drain tube
The connection point is located on the bottom of the device. The condensate drain must be implemented by connecting the
supplied flexible hose to the condensate drain connection. A siphon must be made with the tube (Fig. 6,7) to prevent the
formation of air bubbles.
Piping connection
(fig.8)
The device fittings have a nominal diameter of 160 mm. Rigid or flexible pipes
can be connected to the device inlets. Below is an illustration of each
connection with a specification also of the directions of origin and supply of
the relative air flow.
ATTENTION:
For passivhaus compliant systems, it will be necessary to
install silencers on all 4 air vents.
ENGLISH
5
5a
5a
6
h > 50 mm
∆
≥ 60 mm
7
8
MANDATA
ARIA VIZIATA
VERSO
L’ESTERNO
ASPIRAZIONE
ARIA FRESCA
DALL’
ESTERNO
ASPIRAZIONE
ARIA VIZIATA
DA
CASA
MANDATA
ARIA FRESCA
IN
CASA
Содержание VORT HR 450 Avel D
Страница 3: ...3 Vortice ZH 142 142 144 145 147 148 149 151 164...
Страница 142: ...142 Vort HR 450 Avel D EC 85 Vortice 8 Vortice Vortice Vortice...
Страница 143: ...143 45 C 3mm III M 220 240V 230V A 1 1 A...
Страница 144: ...144 3 4 2 ABS 1 2 3 2 1 PPE 4 5 93 G4 6 G4 7 2 8 LCD 9 4 10 3 4 5 2 2A 2 3 4 5 6 7 8 9 10 2 1 2A 2A...
Страница 145: ...145 6 7 8 160mm 5 5a 5a 6 h 50 mm 60 mm 7 8...
Страница 146: ...146 9 10 11 12 9 10 10 11 11 12 12...
Страница 150: ...150 7 8 23 9 MBUD ID 1 2 10 11 12 13 30 1 14 15 23 16 MBUD ID 1 3 17 30 3 2 6 Progr Prg 30 30 30 0 PRG Crono...
Страница 151: ...151 3 A B 1 2 T Ext T Int T Exh T Sup 3 4 OFF 1 2 3 Boost 5 6 A B 1 2 3 4 5 6...
Страница 163: ...163 INFO S 0 9 6 6 M 0 9 6 4 CFG 6 4 MAIN MENU ALARM SETUP INFO...
Страница 164: ...164 16 17 18 6 19 19A 17 17 18 18 16 16 19 19 A...
Страница 165: ...165...
Страница 179: ...179 16 0 Er01 1 Er02 2 Er03 3 Er04 4 Er05 5 Er06 6 Er07 7 Er08 45 8 Er09 45 9 Er10 10 Er11 11 Er12 12 Er13 VOC...
Страница 180: ...180 Note...
Страница 181: ...181 Note...
Страница 182: ...182 Note...
Страница 183: ...183 Note...